Pressure Relief Systems

PSV Header Design: API 521 Engineering Guide

Design relief valve headers using API 521 methods for pressure drop calculations, sizing for multiple relief scenarios, backpressure limits, and compliance with ASME Section VIII requirements.

Conventional PSVs

Built-up BP ≤ allowable overpressure

API 520-I 5.3.3.1.3: allowable built-up backpressure equals the allowable overpressure, typically 10% of set pressure.

Balanced bellows

About 50% total backpressure

API 520-I 5.3.3.2.1: balanced valves typically apply up to about 50% of set pressure; the manufacturer sets the limit and Kb.

Sizing margin

10-20% oversizing

Header typically sized 10-20% larger than calculated to account for future tie-ins.

Use this guide when you need to:

  • Size relief header piping for single or multiple PSVs.
  • Calculate backpressure and verify PSV capacity.
  • Design headers for future expansion capacity.

1. Overview & Applications

Pressure Safety Valve (PSV) headers collect relieved fluids from multiple relief valves and route them to safe disposal (flare, vent stack, or catch tank). Proper header design ensures backpressure remains within allowable limits for all credible relief scenarios.

[IMAGE 1: PSV Header System Schematic]

Isometric view of typical PSV header arrangement showing multiple PSVs, branch connections, main header, knockout drum, and flare tip.

Gas plants

Low-pressure headers

Multiple process vessels relieve to common LP flare header (typically < 50 psig).

Refineries

Segregated systems

Separate headers for low/high pressure, clean/sour service, vapor/liquid relief.

Compressor stations

High-pressure headers

Station relief headers handle full-bore rupture disks and thermal relief valves.

Offshore platforms

Compact routing

Space-constrained headers require careful optimization for pressure drop.

Key Design Criteria

  • Backpressure limit: Back pressure must stay within the limit for the valve type (API 520-I 5.3.3): built-up up to the allowable overpressure for conventional valves, total up to about 50% of set for balanced valves, manufacturer limit for pilot operated valves
  • Relief scenario: Size for credible simultaneous relief cases (fire case often governs)
  • Pressure drop: Minimize ΔP through proper sizing, minimize fittings, avoid liquid slugs
  • Vapor-liquid separation: Knockout drums upstream of flare to remove entrained liquids
  • Layout considerations: Slope for drainage, support for thermal expansion, isolation for maintenance
Why header design matters: Undersized headers cause excessive backpressure, reducing PSV capacity below required relief rate → potential overpressure. Oversized headers waste capital. Proper design balances safety, cost, and future expansion needs.

Design Standards

Standard Scope Key Requirements
API 521 Pressure-relieving and depressuring systems Relief scenarios, sizing methods, backpressure limits, flare system design
ASME Section VIII Div 1 Pressure vessel code PSV selection, nameplate capacity, overpressure limits (10% / 16% / 21%)
API 520 Part I Sizing, selection, and installation of PSVs Gas/vapor, liquid, two-phase relief sizing equations
API 520 Part II Sizing for fire and runaway reaction Fire exposure area, runaway reaction methods (DIERS)
ASME B31.3 Process piping code Header pipe wall thickness, material selection, support spacing

2. API 521 Design Methodology

API 521 provides comprehensive guidance for designing pressure relief systems including relief valve sizing, header piping, knockout drums, and flare systems.

Relief Scenarios

API 521 Section 4 defines credible overpressure scenarios to consider:

Scenario Description Typical Relief Rate
Fire exposure (pool fire) Vessel exposed to external fire, liquid vaporizes Q = 21,000 × F × A^0.82 (Btu/hr), A = wetted surface area (ft²)
Blocked outlet Downstream valve closed, continued feed to vessel Maximum feed rate (pump/compressor capacity)
Utility failure (cooling loss) Cooling water failure, condenser ineffective Heat duty that must be relieved as vapor
Runaway reaction Exothermic reaction loses temperature control DIERS method or adiabatic calorimetry (VSP2, RSST)
Tube rupture (heat exchanger) High-pressure side leaks into low-pressure side Orifice flow from HP to LP (limited by tube ID)
Thermal expansion Liquid-full vessel heated (solar, jacket, ambient) Volume expansion rate = β × V × dT/dt
Reflux failure (distillation) Loss of overhead condenser, column pressure rises Reboiler duty converted to vapor

Fire Case Sizing (API 521 Section 4.4.12)

Fire Exposure Heat Input: Q = 21,000 × F × A^0.82 (Btu/hr) Where: Q = Total heat input from fire F = Environment factor F = 1.0 for bare steel or insulated with damaged insulation F = 0.3 for insulation in good condition (≥ 2 in thickness) A = Total wetted surface area exposed to fire (ft²) Wetted Surface Area (vertical vessel): A = π D L_w Where: D = Vessel diameter (ft) L_w = Wetted height (ft) = liquid level during fire For horizontal vessel: Use equations in API 521 Figure 15 based on liquid level Relief Rate (gas/vapor): W = Q / (λ × K_d) (lb/hr) Where: λ = Latent heat of vaporization at relief pressure (Btu/lb) K_d = 1.0 for unstable fluids (light hydrocarbons) K_d = 0.5 for stable fluids (may credit depressuring) Example: Propane storage sphere, D = 30 ft, 50% full Wetted area A = π × 30 × 15 = 1414 ft² F = 1.0 (bare steel) Q = 21,000 × 1.0 × 1414^0.82 = 8.05 MMBtu/hr Propane at 150 psig relief: λ = 125 Btu/lb W = 8,050,000 / 125 = 64,400 lb/hr relief rate

Simultaneous Relief Scenarios

For facilities with multiple vessels, determine credible combinations of simultaneous relief:

  • Single equipment failure: One PSV relieves at nameplate capacity, all others closed (most common basis)
  • Fire scenario: All vessels within fire exposure zone relieve simultaneously (pool fire or jet fire diameter)
  • Common cause failure: Utility failure (cooling water, electric power) affects multiple units
  • Domino effect: Relief from one vessel triggers relief in downstream vessels (rare, conservative)
Credible vs incredible scenarios: API 521 does not require sizing for "incredible" scenarios like simultaneous failure of multiple independent systems. Use engineering judgment and company standards to define credible cases. Fire case often governs for gas plants and tank farms.

Overpressure Allowances (ASME Section VIII)

Allowable Overpressure: Single PSV installation: P_relief ≤ MAWP × 1.10 (10% overpressure, operating case) P_relief ≤ MAWP × 1.16 (16% overpressure, fire case) Multiple PSV installation: First valve: P_set ≤ MAWP Second valve: P_set ≤ MAWP × 1.05 Accumulation: P_max ≤ MAWP × 1.16 (operating), 1.21 (fire) Where: MAWP = Maximum Allowable Working Pressure (design pressure) P_set = PSV set pressure (psig) P_relief = Actual vessel pressure during relief For unfired vessels, 10% accumulation is standard for operating cases. For fire exposure, 16% or 21% accumulation is allowed (20% most common).

3. Pressure Drop Calculations

Pressure drop in relief headers reduces PSV capacity. Accurate calculation ensures backpressure remains within allowable limits.

[IMAGE 3: Pressure Drop Components in Header]

Diagram showing pressure profile along header with contributions from friction (pipe segments), fittings (elbows, tees), and acceleration effects.

Gas/Vapor Pressure Drop (Darcy-Weisbach)

Frictional Pressure Drop (incompressible approximation): ΔP = f × (L/D) × (ρ V² / 2g_c) Where: f = Darcy friction factor (dimensionless) L = Pipe length (ft) D = Pipe inside diameter (ft) ρ = Gas density at flowing conditions (lb/ft³) V = Gas velocity (ft/s) g_c = Gravitational constant = 32.2 lbm·ft/lbf·s² For Mach number Ma < 0.3, incompressible approximation is valid. Friction Factor (turbulent flow): 1/√f = -2.0 log₁₀(ε/(3.7D) + 2.51/(Re√f)) (Colebrook equation) Or use Swamee-Jain explicit approximation: f = 0.25 / [log₁₀(ε/(3.7D) + 5.74/Re^0.9)]² Where: ε = Pipe roughness (ft), typically 0.00015 ft for carbon steel Re = Reynolds number = ρ V D / μ μ = Dynamic viscosity (lb/ft·s) Velocity Calculation: V = W / (ρ × A) Where: W = Mass flow rate (lb/s) A = Pipe cross-sectional area = π D² / 4 (ft²)

Pressure Drop in Fittings

Fittings (elbows, tees, valves) cause additional pressure drop expressed as equivalent length or resistance coefficient:

Equivalent Length Method: ΔP_total = f × (L_pipe + Σ L_e) / D × (ρ V² / 2g_c) Where: L_e = Equivalent length of fitting (ft) Typical L/D ratios (equivalent length / diameter): 90° elbow (standard radius): L/D = 30 90° elbow (long radius): L/D = 16 45° elbow: L/D = 15 Tee (flow through run): L/D = 20 Tee (flow through branch): L/D = 60 Gate valve (fully open): L/D = 8 Globe valve (fully open): L/D = 340 Resistance Coefficient Method: ΔP_fitting = K × (ρ V² / 2g_c) Where K = resistance coefficient (dimensionless) 90° elbow: K = 0.9 (standard), 0.6 (long radius) Tee (branch): K = 1.8 Sudden contraction (d/D = 0.5): K = 0.38 Sudden expansion (d/D = 0.5): K = 0.56 Total pressure drop: ΔP_total = (f L/D + Σ K) × (ρ V² / 2g_c)

Compressible Flow Pressure Drop

For high pressure drop (ΔP/P > 10%) or high velocity (Ma > 0.3), use compressible flow equations:

Isothermal Compressible Flow (Crane TP-410 Eq. 1-27, the complete isothermal equation): P₁² - P₂² = [f × L / D + Σ K + 2 × ln(P₁ / P₂)] × G² × Z × R × T / (MW × g_c × 144) Where: P₁ = Inlet pressure (psia) P₂ = Outlet pressure (psia) G = Mass flux = W / A (lb/ft²·s) Z = Compressibility factor (dimensionless) R = 10.73 psia·ft³/(lbmol·°R) [equivalent to 1545 ft·lbf/(lbmol·°R) ÷ 144 in²/ft²] T = Gas temperature (°R) MW = Molecular weight (lb/lbmol) g_c = 32.174 lbm·ft/(lbf·s²) The factor of 144 converts ft² to in² so the result is in psia². Solve for P₂ given P₁, or iterate if both are unknown. Choked Flow Limit: Maximum velocity = sonic velocity at throat V_max = √(k g_c R T / MW) For ideal gas, k = Cp/Cv ≈ 1.3 for natural gas If calculated velocity exceeds sonic velocity, flow is choked. Pressure drop is limited by choked flow condition.

Adiabatic Flow (Fanno)

Crane TP-410 (p. 1-11) notes that gas discharging from a reasonably short pipe into a larger area is usually treated as adiabatic, and that the simple friction flow is the Fanno flow. Long headers with good heat transfer are closer to isothermal. The calculator's adiabatic option solves the Fanno relations with the same friction term K = f × L / D as the isothermal option:

KFanno(M) = (1 − M²) / (k M²) + (k + 1) / (2k) × ln[ (k + 1) M² / (2 + (k − 1) M²) ] KFanno(M₁) − KFanno(M₂) = f × L / D P / P* = (1 / M) × √[ (k + 1) / (2 + (k − 1) M²) ] M₁ = G / (P₁ × s), s = √(k g_c × 144 × MW / (Z R T₁)) T₂ / T₁ = (1 + (k − 1) M₁² / 2) / (1 + (k − 1) M₂² / 2) Check values: k = 1.4, M = 0.5 → KFanno = 1.0691, P/P* = 2.1381. If the pipe reaches M₂ = 1 before the exit, it is choked: the inlet pressure is the choked value and the pressure at the pipe end is P*, above the exit pressure.

Gas Properties and Fittings in the Calculator

  • Compressibility Z: API 520-I 5.6.3 evaluates Z at the inlet relieving conditions, so the PSV rated capacity uses Z at the relieving pressure and temperature. The header pressure drop uses Z at the mean pressure of the header, found together with the pressure drop. Both come from the Dranchuk-Abou-Kassem fit of the Standing-Katz chart with Sutton pseudo-critical properties (GPSA Section 23), valid for natural gas of gravity 0.57 to 1.68; enter Z to use one value for both.
  • Gas viscosity: GPSA Dean and Stiel relations (Eq. 23-20 to 23-22), low pressure value, for natural gas (MW 16 to 30); 0.010 cP otherwise, or the value entered. Its effect on the friction factor at header Reynolds numbers is negligible.
  • Fittings: elbows, gate valves and tees add Crane TP-410 resistance coefficients to f L/D: K = N f_T for elbows and valves (A-28 to A-30) and the flow-split equations 2-35 to 2-38 for tees. No exit loss is added: the exit pressure is the pressure the gas discharges to (API 520-II 6.3.1).

Example: Header Pressure Drop Calculation

Given: Header: 8" Sch 40 (ID = 7.981 in = 0.665 ft) Flow rate: 50,000 lb/hr = 13.89 lb/s natural gas Gas properties: MW = 19, T = 100°F = 560°R, μ = 0.011 cP = 7.4×10⁻⁶ lb/ft·s Header pressure: P₁ = 100 psia (medium-pressure PSV header) Layout: 200 ft straight pipe + 4 elbows (90° LR) + 1 tee (branch) Step 1: Calculate gas density Z = 0.98 ρ = P MW / (Z R T) = 100 × 19 / (0.98 × 10.73 × 560) = 0.323 lb/ft³ Step 2: Calculate velocity A = π × 0.665² / 4 = 0.347 ft² V = W / (ρ A) = 13.89 / (0.323 × 0.347) = 124 ft/s Check Mach number: a = √(k g_c R T / MW) = √(1.3 × 32.2 × 1545 × 560 / 19) = 1381 ft/s Ma = V / a = 124 / 1381 = 0.09 (subsonic, incompressible approximation valid) Step 3: Calculate friction factor Re = ρ V D / μ = 0.323 × 124 × 0.665 / (7.4×10⁻⁶) = 3.6×10⁶ ε/D = 0.00015 / 0.665 = 0.00023 f = 0.25 / [log₁₀(0.00023/3.7 + 5.74/(3.6×10⁶)^0.9)]² = 0.014 Step 4: Calculate total resistance L_e = 4 × 16D + 1 × 60D = 124D = 124 × 0.665 = 82.5 ft L_total = 200 + 82.5 = 282.5 ft Step 5: Calculate pressure drop (isothermal) G = W / A = 13.89 / 0.347 = 40.0 lb/ft²·s P₁² - P₂² = (f L/D) × G² × Z × R × T / (MW × g_c × 144) = (0.014 × 282.5/0.665) × (1600 × 0.98 × 10.73 × 560) / (19 × 32.2 × 144) = 5.95 × 9,422,000 / 88,100 = 636 psia² P₂² = 10,000 - 636 = 9,364 P₂ = 96.8 psia ΔP = 100 - 96.8 = 3.2 psi (3.2% of inlet pressure) This is acceptable for most applications (< 10% backpressure).

Design Guidelines for Low Pressure Drop

  • Limit velocity: Keep Ma < 0.5 (typically V < 0.5 × sonic velocity) to minimize pressure drop and noise
  • Minimize fittings: Use long-radius elbows, avoid globe valves, minimize tees on branch flow
  • Avoid flow restrictions: No orifices, strainers, or small-bore piping in relief header
  • Size conservatively: Add 10-20% margin to calculated header diameter for future tie-ins
  • Slope for drainage: 1/8 to 1/4 in/ft slope toward low point drain to remove condensate

4. Backpressure Limits & PSV Types

Backpressure in the discharge piping affects PSV capacity and operational stability. Different PSV types tolerate different backpressure levels.

[IMAGE 2: PSV Types Cross-Section Comparison]

Side-by-side cross-sectional diagrams of conventional, balanced bellows, and pilot-operated PSVs showing internal components and backpressure effects.

Types of Backpressure

Superimposed Backpressure: Pressure in discharge header when PSV is closed (static condition) Caused by: Other PSVs discharging, header elevation, flare system pressure Built-up Backpressure: Additional pressure rise when this PSV opens and discharges Caused by: Friction and momentum change in discharge piping Total Backpressure: P_back,total = P_superimposed + P_built-up PSV capacity must be corrected for total backpressure.

PSV Type Selection Based on Backpressure

PSV Type Back pressure limit (API 520-I 5.3.3) Capacity correction Kb
Conventional (spring-loaded) Built-up backpressure up to the allowable overpressure, P_B = MAWP × (1 + %AA) − P_set (Eq. 1); typically 10% of set. A constant superimposed backpressure can be offset in the spring setting (5.3.3.1.4). 1.0 within the limit at critical flow. None defined above it; specify a balanced or pilot operated valve (5.3.3.1.5).
Balanced bellows Total (superimposed + built-up) backpressure up to about 50% of set; use where backpressure is high or varies widely (5.3.3.2.1). Manufacturer value. Figure 31 (gas) is a preliminary chart valid to 50% of set (5.3.3.2.3).
Pilot-operated Lift is not affected by backpressure; no API 520-I percentage limit, the manufacturer sets it (5.3.3.3). 1.0 at critical flow; Eq. (16) with F₂ if flow is subcritical.

Capacity Correction for Backpressure

API 520-I back pressure correction (K_b): Conventional valves: K_b = 1.0 while built-up backpressure is within the allowable overpressure (gases at critical flow, or liquids; 5.3.3.1.5). Above it the standard gives no correction. Balanced valves: K_b is the manufacturer's value at the actual backpressure (5.3.3.2). The same value is used in Eq. (6): A = W / (C K_d P₁ K_b K_c) × √(TZ/M). Pilot-operated valves: K_b = 1.0 at critical flow (5.3.3.3). Sizing a balanced valve is a two-step process (5.3.4.2): size with K_b = 1.0 or an assumed value, size the discharge line, calculate the backpressure, then recheck the capacity with the manufacturer K_b. Example (K_b from the manufacturer, assumed here for illustration): Set pressure: 100 psig, backpressure 30 psig (30% of set), manufacturer K_b = 0.90 Effective capacity = rated capacity × K_b If rated W = 10,000 lb/hr, effective W = 10,000 × 0.90 = 9,000 lb/hr Must verify: required relief rate ≤ 9,000 lb/hr If required rate is 9,500 lb/hr → PSV is undersized, use a larger orifice or reduce backpressure

Superimposed Backpressure Sources

  • Other PSVs discharging: Calculate pressure drop from other relief sources to this PSV's connection point
  • Header static pressure: If header vents to flare tip elevated 100 ft, static pressure ≈ 4-5 psi (0.5 psi per 10 ft elevation for gas)
  • Flare system pressure drop: Knockout drum, liquid seal, molecular seal, or flare tip restriction
  • Blowdown/depressuring flow: If depressuring valves discharge to same header, add that flow to backpressure calculation
Backpressure calculation sequence: (1) Define relief scenario (which PSVs discharge simultaneously). (2) Calculate flow rate and pressure drop from each source to confluence points. (3) Sum flows in header and calculate cumulative pressure drop to flare. (4) Work backward to calculate backpressure at each PSV. (5) Verify backpressure < allowable limit for PSV type. (6) If exceeded, increase header size or change PSV type.

5. Multiple Relief Scenarios

Relief headers must accommodate all credible combinations of simultaneous PSV discharges. Proper scenario analysis ensures adequate capacity for worst-case conditions.

[IMAGE 4: Header Segment Flow Analysis]

Plan view schematic showing header segments with cumulative flow rates, branch connections from PSVs, and backpressure calculation points.

Relief Scenario Matrix

Develop a matrix of credible scenarios and calculate header loading for each:

Scenario PSVs Discharging Total Flow (lb/hr) Governing Header Section
Case 1: PSV-101 only PSV-101 (vessel V-101 fire) 50,000 Branch A to main header
Case 2: PSV-201 only PSV-201 (compressor high discharge) 35,000 Branch B to main header
Case 3: Pool fire (south area) PSV-101, PSV-102, PSV-103 120,000 Main header (sections A+B+C)
Case 4: Cooling water failure PSV-201, PSV-202 (both compressors) 70,000 HP header to LP header
Case 5: Blowdown + relief PSV-301 + depressuring valve XV-301 80,000 Section to flare knockout drum

Header Segment Analysis

Divide header into segments and track cumulative flow through each segment:

Segmented Pressure Drop Calculation: For header with multiple branch connections: Segment 1: PSV-A connection to PSV-B connection Flow = W_A ΔP₁ = f(W_A, D₁, L₁) Segment 2: PSV-B connection to PSV-C connection Flow = W_A + W_B ΔP₂ = f(W_A + W_B, D₂, L₂) Segment 3: PSV-C connection to flare Flow = W_A + W_B + W_C ΔP₃ = f(W_A + W_B + W_C, D₃, L₃) Total pressure drop: ΔP_total = ΔP₁ + ΔP₂ + ΔP₃ Backpressure at PSV-A: P_back,A = P_flare + ΔP₁ + ΔP₂ + ΔP₃ Backpressure at PSV-B: P_back,B = P_flare + ΔP₂ + ΔP₃ Backpressure at PSV-C: P_back,C = P_flare + ΔP₃ Check each PSV for allowable backpressure limit.

Header Sizing Strategy

  1. Identify scenarios: List all credible single and multiple PSV discharge cases
  2. Calculate relief rates: For each scenario, determine mass flow rate from each PSV (API 520 sizing equations)
  3. Preliminary header sizing: Size each segment for maximum flow using velocity limit (e.g., Ma < 0.5 or V < 200 ft/s)
  4. Calculate pressure drop: For each scenario, calculate backpressure at each PSV using segmented analysis
  5. Check capacity: Verify PSV capacity (corrected for backpressure) exceeds required relief rate
  6. Iterate if needed: If backpressure exceeds limit, increase header diameter in critical segments
  7. Add margin: Upsize header by 10-20% or one pipe schedule for future tie-ins

Example: Gas Plant Flare Header

System: - 3 process vessels with PSVs (set pressures 150, 200, 250 psig) - LP flare header (design pressure 50 psig) - Flare knockout drum at 15 psig Fire Scenario (governing case): PSV-101: 80,000 lb/hr at 150 psig set PSV-102: 60,000 lb/hr at 200 psig set PSV-103: 40,000 lb/hr at 250 psig set Header Layout: Segment A: PSV-101 to confluence (12" header, 150 ft) Segment B: PSV-102 to confluence (10" header, 100 ft) Segment C: PSV-103 to confluence (8" header, 80 ft) Segment D: Confluence to flare KO drum (16" header, 300 ft) Pressure Drop Calculations: Segment A: W = 80,000 lb/hr, D = 12", L = 150 ft → ΔP_A = 0.8 psi Segment B: W = 60,000 lb/hr, D = 10", L = 100 ft → ΔP_B = 0.9 psi Segment C: W = 40,000 lb/hr, D = 8", L = 80 ft → ΔP_C = 0.7 psi Segment D: W = 180,000 lb/hr, D = 16", L = 300 ft → ΔP_D = 1.5 psi Flare KO drum pressure: 15 psig Backpressure at Each PSV: PSV-101: P_back = 15 + 0.8 + 1.5 = 17.3 psig (11.5% of a 150 psig set) → above 10%, so balanced bellows, with the manufacturer K_b PSV-102: P_back = 15 + 0.9 + 1.5 = 17.4 psig (8.7% of a 200 psig set) → within about 50%, K_b from the manufacturer PSV-103: P_back = 15 + 0.7 + 1.5 = 17.2 psig (6.9% of a 250 psig set) → within about 50%, K_b from the manufacturer All PSVs are well within about 50% of set pressure → acceptable for balanced bellows valves; confirm K_b with the manufacturer

Common Design Mistakes

  • Ignoring superimposed backpressure: Must include flare system pressure, not just header friction drop
  • Using nameplate capacity without backpressure correction: PSV capacity decreases with backpressure (K_b factor)
  • Undersizing branch connections: Branch piping from PSV to header can have higher velocity than main header
  • Not accounting for future expansion: Adding PSVs later requires re-analysis of all scenarios
  • Mixing incompatible fluids: Don't combine acid gas with sweet gas, or oxygen-rich with flammable streams
  • Inadequate drainage: Liquid slugs in vapor header cause water hammer and backpressure spikes
Design for flexibility: Size header 10-20% larger than calculated minimum to accommodate future debottlenecks, process changes, or additional PSV tie-ins. This margin is cheaper to install during initial construction than to replace piping later. Document assumptions and limitations in design basis for future reference.

Frequently Asked Questions

What is a PSV header?

A PSV header is a common collection pipe that receives discharge from multiple pressure safety valves and routes flow to a disposal system such as a flare.

What standards govern PSV header design?

API 521 provides methodology for PSV header sizing, pressure drop calculations, and backpressure limits, while ASME Section VIII covers pressure vessel requirements.

Why are backpressure limits important in PSV header design?

Excessive backpressure in the header can reduce relief valve capacity and prevent proper opening, compromising overpressure protection.