NEC Ampacity, Voltage Drop & Conduit Sizing
Typical: 0.80-0.90 (motors), 1.0 (resistive heaters)
NEC recommends 3% branch, 5% total
NEC base: 86°F (30°C). Higher temps reduce ampacity.
Understand NEC cable sizing methodology, voltage drop calculations, ampacity derating, and hazardous area wiring requirements
Cable sizing per NEC involves three checks: (1) Ampacity - the cable must carry the full load current with appropriate derating factors for temperature, conduit fill, and continuous load per NEC Table 310.16; (2) Voltage drop - typically limited to 3% for branch circuits and 5% total per NEC 210.19 Informational Note; (3) Short circuit withstand - the cable must survive fault current for the clearing time of the protective device.
NEC 210.19 Informational Note No. 4 recommends a maximum of 3% voltage drop for branch circuits and 5% total (feeder plus branch circuit combined). While these are recommendations rather than mandatory requirements, most engineers and inspectors treat 3% as the practical maximum for branch circuits in industrial facilities.
NEC 430.22 requires that branch circuit conductors supplying a single motor have an ampacity not less than 125% of the motor full-load current. This accounts for motor starting inrush, service factor, and temperature rise during continuous operation. The 125% factor ensures cables do not overheat during sustained motor operation.
In Class I Division 1 and Division 2 hazardous areas per NEC 500-503, cables must be installed in rigid metal conduit or MI cable, with explosion-proof seals at boundaries. Cable types must be rated for the environment (THHN/THWN-2 or XHHW-2). API RP 14F provides additional guidance for cable installation in petroleum facilities including minimum cable sizes and routing requirements.