Facility Design & Electrical

Electrical Cable Sizing

Fundamentals of NEC cable sizing for power distribution in midstream oil and gas facilities. Covers ampacity selection, voltage drop analysis, derating factors, motor circuit requirements, and hazardous area wiring per API RP 14F.

NEC Reference

Article 310

Conductor ampacity tables and derating.

Motor Circuits

125% FLA

NEC 430.22 conductor sizing requirement.

Max Voltage Drop

3% Branch

NEC 210.19 recommended limit for branch circuits.

1. Cable Sizing Overview

Electrical cable sizing is the process of selecting the appropriate conductor size to safely and efficiently deliver power from the source to the load. In oil and gas facilities, proper cable sizing is critical for equipment performance, personnel safety, and regulatory compliance.

Three Essential Checks

Every cable must satisfy three independent requirements: (1) ampacity adequate for the load current with all applicable derating factors, (2) voltage drop within acceptable limits for the cable run length, and (3) short circuit withstand capacity exceeding the available fault current for the protective device clearing time. The cable size is determined by whichever check requires the largest conductor.

Governing Standards

Standard Scope Application
NEC (NFPA 70) National Electrical Code Primary code for all electrical installations in the US
NEC Article 310 Conductors for General Wiring Ampacity tables, derating factors, insulation ratings
NEC Article 430 Motors and Motor Circuits 125% FLA sizing, overcurrent protection, motor feeders
IEEE 141 (Red Book) Industrial Power Distribution System design, voltage drop, short circuit analysis
API RP 14F Electrical Installations Petroleum production facilities electrical design
NEC Articles 500-503 Hazardous Locations Wiring methods for Class I Division 1 and Division 2

Common Cable Types in Oil & Gas

Insulation Rating Application
THHN/THWN-2 90°C dry, 75°C wet Most common for conduit installations, dry/damp/wet locations
XHHW-2 90°C dry & wet Cable tray, direct burial, moisture resistance
USE-2 90°C Underground service entrance, direct burial
MI (Mineral Insulated) 250°C Fire-rated applications, hazardous areas
MC Cable 90°C Metal clad, Class I Div 2 areas (NEC 501.10(B))

2. Load Current Calculations

The first step in cable sizing is determining the full load current (FLA) that the cable must carry. The calculation method depends on the load type and phase configuration.

Motor Full Load Current

For motors, the full load current is calculated from the horsepower rating, voltage, efficiency, and power factor:

Three-Phase Motor:

FLA = (HP × 746) / (√3 × V × η × PF)

Single-Phase Motor:

FLA = (HP × 746) / (V × η × PF)

Where HP is motor horsepower, V is line voltage in volts, η is motor efficiency (decimal), and PF is power factor (decimal). The factor 746 converts horsepower to watts.

Resistive and General Loads

Three-Phase Load:

I = (kW × 1000) / (√3 × V × PF)

Single-Phase Load:

I = (kW × 1000) / (V × PF)

For purely resistive loads like electric heaters, the power factor is 1.0 and efficiency is not applicable because input power equals output power.

Typical Power Factor and Efficiency Values

Load Type Power Factor Efficiency Notes
Induction motor (loaded) 0.80 – 0.90 85 – 96% PF improves with load; premium efficiency motors >93%
Induction motor (lightly loaded) 0.50 – 0.70 70 – 85% PF drops significantly below 50% load
Electric heater 1.00 100% Purely resistive load
Lighting (fluorescent/LED) 0.90 – 0.99 N/A Electronic ballasts improve PF
VFD-driven motor 0.95 – 0.99 85 – 96% VFD input PF is near unity; cable to motor sized for full speed current

NEC Table Values vs. Calculated FLA

NEC Article 430 provides full load current tables (Table 430.247 for DC motors, 430.248 for single-phase, 430.250 for three-phase). In practice, many engineers use nameplate data or calculated values. When using NEC tables for overcurrent protection sizing, the table values take precedence over nameplate data per NEC 430.6.

3. NEC Ampacity Selection

Ampacity is the maximum current a conductor can carry continuously without exceeding its temperature rating. NEC Table 310.16 provides base ampacities for insulated conductors in raceway, cable, or earth at an ambient temperature of 30°C (86°F).

Ampacity Table Overview (NEC 310.16)

The table provides ampacities at three insulation temperature ratings (60°C, 75°C, and 90°C) for both copper and aluminum conductors.

Wire Size Cu 60°C Cu 75°C Cu 90°C Al 75°C Al 90°C
14 AWG152025
12 AWG2025302025
10 AWG3035403035
8 AWG4050554045
6 AWG5565755060
4 AWG7085956575
2 AWG9511513090100
1/0 AWG125150170120135
4/0 AWG195230260180205
500 MCM320380430310350

Termination Temperature Limitation

Even when using 90°C-rated cable, the ampacity used for sizing is typically limited to the 75°C column. This is because most equipment terminations (breakers, disconnects, motor terminals) are rated for 75°C. The 90°C rating is used only for calculating the benefit of temperature derating. This critical distinction is addressed in NEC 110.14(C).

Conductor Material Selection

Copper conductors are standard in most industrial applications due to higher conductivity and smaller required sizes. Aluminum conductors are sometimes used for large feeders and services where the cost savings of aluminum outweigh the larger conduit and connection requirements.

Property Copper Aluminum
Conductivity (% IACS) 100% 61%
Typical size premium Baseline 1-2 sizes larger for equivalent ampacity
Weight Heavier ~50% lighter for same ampacity
Termination Standard lugs Requires AL-rated lugs, anti-oxidant compound
Hazardous areas Preferred Permitted but less common

4. Derating Factors

Base ampacity values from NEC Table 310.16 assume specific installation conditions. When actual conditions differ, correction factors must be applied to reduce the allowable ampacity.

Temperature Correction (NEC 310.15(B)(1))

When ambient temperature exceeds 30°C (86°F), the ampacity must be reduced to prevent the conductor from exceeding its insulation temperature rating. Conversely, lower ambient temperatures allow increased ampacity.

Ambient Temp (°C) Ambient Temp (°F) 90°C Insulation Factor 75°C Insulation Factor
21-2570-771.041.05
26-3079-861.001.00
31-3588-950.960.94
36-4097-1040.910.88
41-45106-1130.870.82
46-50115-1220.820.75
51-55124-1310.760.67
56-60133-1400.710.58

90°C Insulation Advantage

Using 90°C-rated insulation (THHN, XHHW-2) provides a significant advantage in hot environments. At 50°C ambient, 90°C insulation retains 82% of base ampacity while 75°C insulation retains only 75%. This is why 90°C-rated cable is standard in oil and gas facilities where outdoor temperatures and heat from adjacent equipment can be significant.

Conduit Fill Adjustment (NEC 310.15(C)(1))

When more than three current-carrying conductors are installed in a single raceway, the ampacity must be further reduced due to reduced heat dissipation capability.

Number of Current-Carrying Conductors Adjustment Factor
1-31.00 (no adjustment)
4-60.80
7-90.70
10-200.50
21-300.45
31-400.40
41+0.35

Neutral Conductors

A neutral conductor that carries only unbalanced current from other conductors of the same circuit is not counted as a current-carrying conductor (NEC 310.15(E)(1)). However, when the major portion of the load consists of nonlinear loads (such as VFDs or electronic equipment), the neutral may carry harmonic currents and must be counted as a current-carrying conductor.

Combined Derating

When both temperature correction and conduit fill adjustment apply, multiply the factors together to get the combined derating factor. The required cable ampacity is then:

Required Ampacity = Design Current / (Temp Factor × Fill Factor)

Design Current for motors = 1.25 × FLA (per NEC 430.22)

Design Current for continuous loads = 1.25 × FLA (per NEC 210.20(A))

5. Voltage Drop Analysis

Voltage drop occurs as current flows through the resistance and reactance of the cable. Excessive voltage drop reduces motor torque, dims lighting, and can cause equipment malfunction. NEC recommends limiting voltage drop to 3% for branch circuits and 5% total (feeder plus branch combined).

Voltage Drop Equations

Three-Phase:

VD = √3 × L × I × Reff / 1000

Single-Phase:

VD = 2 × L × I × Reff / 1000

Effective Resistance:

Reff = R × cosθ + X × sinθ

Where L is the one-way cable length in feet, I is the load current in amps, and Reff is the effective impedance per 1000 feet combining AC resistance (R) and reactance (X) from NEC Table 9, adjusted for the power factor angle (θ).

Why Use Reff Instead of Just R?

At power factors less than unity, both resistance and reactance contribute to voltage drop. The effective resistance method accounts for the phase angle between voltage and current. For large conductors (4/0 and above), reactance can be a significant portion of impedance, and ignoring it underestimates voltage drop. For small conductors at unity power factor, Reff simplifies to just R.

Voltage Drop vs. Cable Length

Voltage drop is directly proportional to cable length. For long runs common in oil and gas facilities, voltage drop often governs the cable size rather than ampacity.

Scenario Typical Cable Length Sizing Driver
MCC to motor (indoor) 50 – 200 ft Usually ampacity
Substation to MCC 200 – 1000 ft Often voltage drop
Remote well pad power 1000 – 10,000 ft Almost always voltage drop
Pipeline cathodic protection 500 – 5000 ft Voltage drop

Voltage Drop Impact on Motors

Motors are particularly sensitive to voltage drop because torque is proportional to the square of voltage. A 10% voltage drop reduces available starting torque by approximately 19% and can prevent the motor from starting under load.

Voltage Drop Torque Reduction Effect
3%~6%Acceptable for most motors
5%~10%Maximum recommended, marginal starting
10%~19%May not start under load
15%~28%Likely stall, motor damage risk

6. Motor Circuit Requirements

Motor circuits have specific NEC requirements that differ from general branch circuit rules. NEC Article 430 provides comprehensive requirements for motor branch circuit conductors, overcurrent protection, and disconnecting means.

Conductor Sizing (NEC 430.22)

Branch circuit conductors for a single motor must have an ampacity not less than 125% of the motor full-load current rating. This ensures the cable can handle the thermal effect of motor starting and continuous operation.

Minimum Conductor Ampacity = 1.25 × FLA

FLA from NEC Table 430.250 (3-phase) or nameplate

Overcurrent Protection (NEC 430.52)

Motor branch circuit short-circuit and ground-fault protection is sized differently from the conductor. The protective device must be large enough to allow motor starting but small enough to protect against faults.

Protective Device Maximum Size Notes
Inverse-time breaker 250% of FLA Round up to next standard size if needed
Dual-element time-delay fuse 175% of FLA Preferred for motor circuits
Instantaneous-trip breaker 800% of FLA Used only with listed combinations

Overload Protection vs. Short Circuit Protection

Motor overload protection (thermal overload relay, typically 115-125% of FLA) protects the motor from sustained overcurrent. Branch circuit short-circuit protection (breaker or fuse) protects the cable and equipment from fault currents. These are separate protective functions and must not be confused.

Motor Feeder Conductors (NEC 430.24)

When a feeder supplies multiple motors, the conductor ampacity must be at least 125% of the largest motor FLA plus the sum of all other motor FLAs. This accounts for the fact that only one motor experiences starting current at a time under normal conditions.

7. Hazardous Area Wiring

Electrical installations in oil and gas facilities frequently involve Class I hazardous locations where flammable gases may be present. NEC Articles 500-503 and API RP 14F define the wiring methods, materials, and installation practices required for these areas.

Wiring Methods by Classification

Classification Permitted Wiring Methods Key Requirements
Class I, Division 1 Rigid metal conduit (RMC), MI cable, ITC-HL cable Explosion-proof fittings, conduit seals at boundaries, threaded connections
Class I, Division 2 RMC, IMC, MC cable, MI cable, TC cable in trays, PLTC cable Sealed fittings at boundaries, non-incendive equipment
Non-Hazardous Any NEC-permitted method Standard installation practices

Conduit Seals (NEC 501.15)

Conduit seals are required at specific locations to prevent the passage of gases, vapors, or flames from one portion of the electrical system to another. Proper seal installation is critical for the integrity of the hazardous area installation.

Seal Requirements

Seals are required: (1) within 18 inches of each enclosure containing arcing or sparking equipment in Division 1 areas, (2) at the boundary between Division 1 and Division 2, and between classified and unclassified areas, (3) where conduits pass through walls or floors that form the boundary of a classified area. Seal fittings must be accessible and the sealing compound must be approved for the application.

API RP 14F Recommendations

API RP 14F provides additional guidance specific to petroleum production facilities that supplements NEC requirements:

Requirement API RP 14F Guidance
Minimum conductor size 12 AWG minimum for power and lighting circuits in hazardous areas
Cable tray systems Power and control cables may share trays with separation barriers
Grounding Equipment grounding conductor required in every raceway
Cable routing Minimize cable exposure in classified areas; route through non-hazardous areas when practical
Corrosion protection PVC-coated conduit or equivalent in corrosive environments

8. Conduit & Overcurrent Protection

After determining the cable size, the conduit must be sized to accommodate the conductors while maintaining the NEC fill limits for heat dissipation and ease of installation.

Conduit Fill Limits (NEC Chapter 9)

Number of Conductors Maximum Fill (%) Rationale
1 conductor 53% Single conductor, generous fill
2 conductors 31% Moderate restriction for pulling
3 or more 40% Standard fill limit for most installations

Short Circuit Withstand

Cables must be able to withstand the thermal effects of short circuit current for the time required for the protective device to clear the fault. The cable I²t rating must exceed the available fault current squared times the clearing time.

I²t (cable) ≥ Isc² × tclear

Where Isc is the available fault current and tclear is the protective device clearing time (typically 0.05 to 0.5 seconds for breakers)

Practical Short Circuit Check

For most branch circuits in oil and gas facilities, short circuit withstand is not the governing factor because the cable sized for ampacity and voltage drop has more than adequate short circuit capacity. However, this check becomes critical for cables connected to large transformers or generators where available fault current may be very high, and for cables protected by fuses with long clearing times.

Overcurrent Device Selection Summary

Load Type OCPD Sizing NEC Reference
Single motor Max 250% FLA (inverse-time breaker) 430.52, Table 430.52
Continuous load (heater, lighting) 125% of load current 210.20(A), 215.3
Non-continuous general load 100% of load current (next standard size) 240.4
Multi-motor feeder Largest motor OCPD + sum of other FLAs 430.62

Related Resources