1. Radiation governs the height
API 537 §4.13.3.1 is explicit: "the primary criterion used to determine the flare stack height shall be flare flame radiant heat intensity at grade." The stack is raised until the heat flux at the worst-case ground-level receiver falls to the allowable limit. Toxic/CO dispersion is a concern only for an unignited release (the flame consumes the combustibles) and is handled as a separate dispersion study with the appropriate stability class and source term — it is not part of this radiation-based height.
2. Radiation limits (API 521 Table 9)
API 521 Table 9 gives the permissible design radiation for personnel — all four rows are personnel limits (the 9.46 kW/m² row is "urgent emergency action," not an equipment-only zone):
| Exposure scenario | Btu/hr·ft² | kW/m² |
|---|---|---|
| Continuous exposure (appropriate clothing) | 500 | 1.58 |
| Emergency action, 2–3 min | 1500 | 4.73 |
| Emergency action, ≤ 30 s | 2000 | 6.31 |
| Urgent emergency action (shielding/fire suit) | 3000 | 9.46 |
Solar radiation (0.79–1.04 kW/m², i.e. 250–330 Btu/hr·ft²) may be deducted from the limit when sizing for continuous exposure (API 521 §6.4.2.3). Heat flux from a point-source flame, evaluated at the flame centre:
τ = atmospheric transmissivity (≈0.85 clear, lower in humid/long path), F = radiant heat fraction (≈0.2 natural gas, higher for unsaturates/H₂S), Q = ṁ·ΔH_c, R = distance from the flame centre to the receiver. Rearranged, the required flame-centre→receiver distance is D = √(τ·F·Q/(4π·K)) (API 521 Eq 24).
3. Flame length & tip velocity
Flame length comes from the API 521 Fig 8 heat-release curve (the same value is used regardless of tip Mach):
API 521 Annex C worked example: Q = 100,000 lb/hr × 21,500 Btu/lb = 2.15×10⁹ Btu/hr → L ≈ 170 ft. The flare-tip exit velocity is then the actual vapour volumetric flow divided by the tip area (API 521 Eq C.2) — not an assumed value:
For the Annex C example (MW 46.1, 300 °F, 1.53 ft tip) this gives uj ≈ 181 ft/s. The riser velocity should stay ≤ 0.5 Mach (API 537 §4.13.2.2).
4. Flame distortion & sizing
Lateral wind bends the flame. API 521 Figure 9 gives the horizontal and vertical projections of the flame tip as a function of the wind-to-jet velocity ratio:
At u∞/uj = 0.16 the flame is already strongly bent (ΣΔx/L ≈ 0.85, ΣΔy/L ≈ 0.36); at low wind it stands nearly vertical (ΣΔx/L → 0, ΣΔy/L → 1). A simple θ = atan(u∞/uj) badly under-predicts this bend — and using a fixed jet velocity hides it entirely, which is why the actual uj matters. The flame centre is taken at half the distortion, ( ΣΔx/2 , H + ΣΔy/2 ), and placed toward the (downwind) receiver as the worst case. The stack height H is then raised until the flame-centre→receiver distance reaches D from §2.
5. References
- API Std 521 §6.4.2 + Annex C — flame length (Fig 8), tip velocity (Eq C.2), flame distortion (Fig 9), point-source radiation (Eq 24), Table 9 personnel limits.
- API Std 537 §4.13.3 — radiant heat intensity at grade as the primary stack-height criterion; §4.13.2.2 riser ≤ 0.5 Mach.
Ready to size your stack?
→ Launch Calculator