CP Survey Analysis Calculator

NACE SP0207 & SP0169 Pipe-to-Soil Potential Analysis

CP Survey Analysis Calculator (NACE SP0207)
Analyze cathodic protection survey data for buried pipelines. Enter pipe-to-soil potential readings from close-interval surveys (CIS), specify soil conditions and coating type, and evaluate protection adequacy against NACE SP0169 criteria. Includes IR drop correction, coating condition assessment, and remediation recommendations.

Pipe-to-Soil Potential Readings

pts

mV Cu/CuSO4 (negative values, e.g., -920, -850, -780)

If provided, used for IR-free potential and IR drop calculation.

Protection Criteria

mV

Typical bare steel: -500 to -600 mV Cu/CuSO4

mV

More negative than -1200 mV risks coating disbondment and hydrogen embrittlement.

Soil & Coating

ohm-cm
years

Pipeline Parameters

in
ft

Understanding CP Surveys

CP Criteria
The -850 mV Cu/CuSO4 criterion (NACE SP0169) is the most common standard for adequate cathodic protection of buried steel. IR-free (instant-off) potentials must meet this threshold.
IR Drop Correction:
ON potentials include voltage drop through soil resistance. Instant-OFF readings (taken within 0.1-1s of current interruption) remove this IR error for accurate assessment.
Assessment Levels: Adequate (≤ -850 mV OFF) | Marginal (-800 to -850 mV) | Inadequate (> -800 mV) | Overprotected (< -1200 mV)

CP Criteria

V_ps ≤ -850 mV (Cu/CuSO4)
V_ps = Pipe-to-soil potential (IR-free)
-850 mV = NACE SP0169 primary criterion
IR Drop = V_on − V_off
100 mV shift = Alternative: V_off − V_native ≥ 100 mV

Standards & References

  • NACE SP0207
    Performing Close-Interval Potential Surveys and DC Surface Potential Gradient Surveys on Buried or Submerged Metallic Pipelines
  • NACE SP0169
    Control of External Corrosion on Underground or Submerged Metallic Piping Systems
  • 49 CFR 192.463
    External corrosion control: Cathodic protection
  • NACE TM0497
    Measurement Techniques Related to Criteria for Cathodic Protection

Engineering Notes

  • IR-Free: Always use instant-OFF potentials for compliance assessment per 49 CFR 192
  • Overprotection: Potentials more negative than -1200 mV can cause coating disbondment and hydrogen damage
  • Soil resistivity: Low resistivity (<2000 ohm-cm) indicates aggressive soil requiring more CP current
  • CIS spacing: NACE SP0207 recommends 2.5-5 ft intervals for adequate resolution

Frequently Asked Questions

What is the -850 mV CP criterion?

The -850 mV Cu/CuSO4 criterion (NACE SP0169 Section 6.2.2.1) is the most widely used cathodic protection criterion for buried steel pipelines. A pipe-to-soil potential of -850 mV or more negative (with cathodic protection applied) indicates adequate protection. This potential must be measured with IR drop compensation to be meaningful.

What is IR drop in CP surveys?

IR drop is the voltage error in pipe-to-soil potential measurements caused by CP current flowing through the soil resistance between the pipe and reference electrode. It makes readings appear more negative than the true polarized potential. IR drop correction methods include instant-off measurements, coupon measurements, and close-interval surveys with current interruption.

What is a close-interval survey (CIS)?

A close-interval survey (CIS) per NACE SP0207 measures pipe-to-soil potentials at closely spaced intervals (typically 2.5 to 5 feet) along the pipeline. Both ON and instant-OFF potentials are recorded. CIS identifies areas of inadequate CP protection, coating damage, shielding, and interference. It is the most comprehensive tool for evaluating external corrosion control.