🏭

Compressor Building Separation Calculator

NFPA 37 fire separation & API RP 500 area classification

How far must a compressor building be from its neighbours?
Computes the NFPA 37 fire separation, the IBC building-code setback (Group H-2), and the API RP 500 electrical keep-out from a natural gas compressor/engine building to another compressor building, an occupied building (control room / MCC), a warehouse, or a production tank — and flags where an API RP 752 consequence siting study governs. Built for lighter-than-air (natural gas) and heavier-than-air service.

Building Geometry (each building)

ft
ft
ft

Layout

ft

Ventilation

cfm

Use the airflow available in the worst-case operating mode (e.g. one fan running). API RP 500 "adequate" = ≥1.0 cfm/ft² and ≥6 ACH.

Fire Protection & Relief

Building Code (IBC, US)

A gas compressor building > 1,000 ft² is commonly Group H-2 → IBC §415.6.4.2 requires a 30 ft setback.

Sets the IBC Table 705.5 exterior-wall fire-rating required below 30 ft.

What this tool does — and doesn't

  • NFPA 37 sets the hard minimum separation; API RP 500 does not mandate a distance — it tells you how the gap is classified at the spacing you choose.
  • An overlapping Division 2 zone between two adequately-ventilated compressor buildings is a normal, code-compliant condition — not a violation.
  • Occupied buildings (control room, MCC) additionally require an API RP 752 consequence-based siting study — the tool gives the grounded floor (fire separation + Division 2 keep-out), not the RP 752 distance. Tanks are governed by their own classification plus NFPA 30 spacing.
  • Relief/blowdown discharge location, a loss-of-ventilation interlock, and owner/insurer facility-siting standards are evaluated as conditions, not distances.
  • Advisory / preliminary screening — confirm on a stamped area-classification drawing and a formal facility-siting study. Consult a qualified engineer.

Standards & References

  • NFPA 37 (2021)
    §4.1.2.2.2 / §4.1.4 — stationary engine building separation
  • API RP 500 (4th ed., 2023)
    §6.3.2.4.2 ventilation; §9.2.2.1 / Fig 23 compressor shelter; §8.2.3.4 relief vents
  • NEC Article 500
    Hazardous (classified) locations — Division
  • 49 CFR 192
    Compressor station design (U.S. gas)

Frequently Asked Questions

How far apart do natural gas compressor buildings need to be?

NFPA 37 §4.1.2.2.2 requires detached engine/compressor buildings to be at least 1.5 m (5 ft) apart, measured from openings and combustible walls. That minimum drops to 0 ft (buildings may be adjacent) if a facing wall has at least a 1-hour fire-resistance rating or a building is protected by an automatic fire-protection system. API RP 500 does not mandate a separation distance but classifies the electrical area in the gap.

What standards govern compressor building spacing?

NFPA 37 governs fire separation of stationary combustion engine buildings, and API RP 500 governs the electrical area classification (Division 1/Division 2) around and between them. Owner or insurer facility-siting standards (and 49 CFR 192 for U.S. gas stations) may impose additional spacing.

Is the gap between two compressor buildings a classified hazardous area?

If the buildings are adequately ventilated, each is Class I, Division 2 with an exterior Division 2 zone extending about 15 ft (4.5 m) for lighter-than-air natural gas (API RP 500 Figure 23). Buildings spaced closer than twice that extent have overlapping envelopes, so the entire gap is Division 2 — acceptable, but all electrical in the gap must be Division 2-rated.

What makes a compressor building adequately ventilated under API RP 500?

API RP 500 §6.3.2.4.2 defines adequate ventilation as at least 1.0 cubic foot per minute of air per square foot of floor area AND at least 6 air changes per hour. Meeting it keeps the interior Class I, Division 2; failing it classifies the interior Division 1 and adds a 10 ft Division 1 transition zone outside the openings.