Equipment Design

Horsepower and Torque Calculations

Understand the relationship between horsepower and torque, size motors and engines for compressors and pumps, select gearboxes and couplings, and calculate starting torque and locked rotor current.

HP-Torque Relation

HP = (T × N) / 5252

Where T = torque (lb-ft), N = speed (RPM). Constant 5252 = 33000/(2π).

Starting torque

150-300% Full Load

Electric motors typically produce 150-300% of full-load torque at startup.

Service factor

1.15-1.25

Motor service factor provides overload capacity for transient conditions.

Use this guide when you need to:

  • Size motors for compressor or pump drives.
  • Calculate required torque at operating speed.
  • Select gearboxes and flexible couplings.
  • Estimate starting current and locked rotor torque.

1. Overview & Applications

Horsepower and torque are fundamental to sizing and selecting prime movers (motors, engines, turbines) for compressors, pumps, and other rotating equipment in midstream facilities.

Compressor drives

Centrifugal/reciprocating

Motor or engine sizing based on horsepower demand at operating conditions.

Pump drives

Centrifugal/positive displacement

Hydraulic power requirements plus mechanical efficiency losses.

Gearbox selection

Speed reduction

Match motor speed to driven equipment speed with proper service factor.

Starting analysis

Locked rotor current

Electrical system must handle inrush current during motor startup.

Key Concepts

  • Horsepower (HP): Rate of doing work; 1 HP = 550 ft-lb/s = 33,000 ft-lb/min = 745.7 watts
  • Torque (T): Rotational force; lb-ft (US) or N·m (SI); 1 lb-ft = 1.356 N·m
  • Speed (N): Revolutions per minute (RPM); synchronous speed = 120f/p where f=frequency, p=poles
  • Efficiency (η): Output/input power ratio; NEMA Premium motors: 91-96% depending on size
  • Service Factor (SF): Continuous overload capacity; typically 1.15 for TEFC motors per NEMA MG-1
Why HP and torque matter: Undersizing a motor results in overload trips and equipment failure. Oversizing wastes capital and reduces efficiency at low loads. Proper sizing requires understanding both steady-state and transient torque demands.

2. Horsepower-Torque Relationship

The fundamental relationship between mechanical power, torque, and rotational speed is derived from the definition of work and power.

Fundamental Equation

Horsepower-Torque Relationship: HP = (T × RPM) / 5252 Where: HP = Horsepower (mechanical) T = Torque (lb·ft) RPM = Rotational speed (revolutions per minute) 5252 = Conversion constant (33000 / 2π) Alternatively: T = (HP × 5252) / RPM Or in SI units: P (kW) = (T × RPM) / 9549 Where T is in N·m

Derivation

From First Principles: Power = Work / Time Work (rotational) = Force × Distance = Torque × Angle P = T × ω (where ω = angular velocity in rad/s) Converting to HP and RPM: ω (rad/s) = (2π × RPM) / 60 P (ft·lb/s) = T (lb·ft) × (2π × RPM) / 60 HP = P / 550 (550 ft·lb/s = 1 HP) HP = [T × (2π × RPM) / 60] / 550 HP = T × RPM × (2π / 33000) HP = T × RPM / 5252 Where 5252 = 33000 / (2π)

Torque vs. Speed Characteristics

Torque-speed characteristics chart showing three load types: blue constant torque curve for reciprocating compressors and PD pumps, red variable torque parabolic curve proportional to N squared for centrifugal equipment, and green constant power hyperbolic curve for machine tools and winders, with power curves on secondary axis
Torque vs speed load profiles for different equipment types. Centrifugal loads (T∝N²) have cubic power relationship with speed, while constant torque loads have linear power increase.
Equipment Type Torque Profile HP Profile Typical Application
Constant torque T = constant HP ∝ RPM Positive displacement pumps, reciprocating compressors
Variable torque (quadratic) T ∝ RPM² HP ∝ RPM³ Centrifugal pumps, centrifugal compressors, fans
Constant power T ∝ 1/RPM HP = constant Machine tools, winders (rare in midstream)

Example Calculation

Calculate torque required for a 500 HP motor operating at 1800 RPM:

Given: HP = 500 RPM = 1800 T = (HP × 5252) / RPM T = (500 × 5252) / 1800 T = 2,626,000 / 1800 T = 1459 lb·ft Check: HP = (1459 × 1800) / 5252 = 500 HP ✓ At half speed (900 RPM) for same power: T = (500 × 5252) / 900 = 2918 lb·ft (double the torque)

Power Forms and Conversions

Common Power Units: 1 HP (mechanical) = 550 ft-lb/s = 33,000 ft-lb/min 1 HP = 745.7 watts (745.699... exact) 1 HP = 0.7457 kW 1 HP = 2545 Btu/hr 1 kW = 1.341 HP Brake Horsepower (BHP): BHP = Power delivered to shaft (measured by dynamometer or calculated) Indicated Horsepower (IHP): IHP = Theoretical power from cylinder pressure (reciprocating compressors/engines) Electrical Input Power (3-phase): kW_in = (HP × 0.7457) / η Amps = (HP × 746) / (√3 × V × η × PF) Where: η = Motor efficiency (0.90–0.96 typical) PF = Power factor (0.85–0.92 at full load) V = Line voltage (460V standard US industrial)

3. Motor/Engine Sizing

Proper motor or engine sizing requires calculating power demand at operating conditions and applying appropriate safety factors for transient loads, efficiency losses, and service conditions.

Compressor Power Calculation

Centrifugal Compressor: BHP = (Q × ρ₁ × R × T₁ × Z_avg / (MW × 33000 × η_poly)) × [(k/(k-1)) × ((r^((k-1)/k)) - 1)] Simplified adiabatic form: BHP = (Q × P₁ × k/(k-1) × 1/(η_adi × 229)) × [(r^((k-1)/k)) - 1] Where: Q = Inlet flow rate (ACFM) P₁ = Inlet pressure (psia) r = Compression ratio (P₂/P₁) k = Specific heat ratio (Cp/Cv ≈ 1.27 for natural gas) η_adi = Adiabatic efficiency (0.75–0.85) Reciprocating Compressor: BHP = (P₁ × Q / (η_mech × 229)) × [(n/(n-1)) × (r^((n-1)/n) - 1)] Where: n = Polytropic exponent (1.25–1.30 for natural gas) η_mech = Mechanical efficiency (0.85–0.92)

Pump Power Calculation

Centrifugal Pump: BHP = (Q × H × SG) / (3960 × η_pump) Where: Q = Flow rate (GPM) H = Total dynamic head (ft) SG = Specific gravity (dimensionless) η_pump = Pump efficiency (0.70–0.85 typical) Positive Displacement Pump: BHP = (Q × ΔP × SG) / (1714 × η_pump) Where: ΔP = Differential pressure (psi) η_pump = Pump efficiency (0.80–0.90 for PD pumps) 1714 = Conversion constant

Motor Sizing Procedure

Step-by-Step Motor Selection: 1. Calculate brake horsepower (BHP) at operating conditions 2. Apply service factor: HP_rated = BHP / SF - SF = 1.0 (continuous duty, constant load) - SF = 1.15 (intermittent duty, standard service) - SF = 1.25 (heavy duty, frequent starts) 3. Select next standard motor size: Standard HP ratings: 1, 1.5, 2, 3, 5, 7.5, 10, 15, 20, 25, 30, 40, 50, 60, 75, 100, 125, 150, 200, 250, 300, 350, 400, 450, 500, 600, 700, 800, 900, 1000, 1250, 1500, 1750, 2000, 2500, 3000 4. Verify motor can handle peak load: HP_peak < HP_rated × SF 5. Check thermal rating (nameplate temperature rise)

Motor Efficiency and Power Factor

Motor Size (HP) NEMA Premium Efficiency Typical Power Factor Full Load Current (460V)
10 91.7% 0.85 14 A
50 93.6% 0.87 62 A
100 95.0% 0.89 120 A
250 95.8% 0.90 288 A
500 96.2% 0.91 570 A
1000 96.5% 0.92 1140 A

Example: Compressor Motor Sizing

Size a motor for a centrifugal compressor with the following operating conditions:

Given: Q = 5000 ACFM (inlet) P₁ = 100 psia P₂ = 500 psia T₁ = 80°F = 540°R η_adi = 0.80 k = 1.27 Calculate compression ratio: r = 500 / 100 = 5.0 Calculate BHP: BHP = (5000 × 100 × 1.27/(1.27-1) × 1/(0.80 × 229)) × [(5.0^0.213) - 1] BHP = (5000 × 100 × 4.70 / 183.2) × [1.408 - 1] BHP = 12,837 × 0.408 BHP = 5238 HP Apply service factor (continuous duty, centrifugal): SF = 1.15 HP_rated = 5238 / 1.15 = 4555 HP Select standard motor: 5000 HP (next size up) Verify peak load capacity: HP_peak (startup surge) ≈ 1.10 × 5238 = 5762 HP HP_available = 5000 × 1.15 = 5750 HP (marginal — consider 6000 HP) Select: 5000 HP if startup is unloaded, or 6000 HP for full-load start margin
Service factor importance: The motor service factor allows brief overloads without damage. A 1.15 SF motor rated at 100 HP can deliver 115 HP continuously at rated voltage and frequency. However, operating above nameplate HP increases temperature rise and reduces motor life.

4. Gearbox and Coupling Selection

Gearboxes provide speed reduction or increase between driver and driven equipment. Flexible couplings accommodate misalignment and dampen torsional vibrations.

Gearbox Speed Ratio

Gear Ratio: Ratio = N_input / N_output = T_output / T_input Where: N_input = Input shaft speed (RPM) N_output = Output shaft speed (RPM) T_output = Output torque (lb·ft) T_input = Input torque (lb·ft) For multi-stage gearbox: Overall ratio = Ratio₁ × Ratio₂ × ... × Ratioₙ Torque and Power Relationship: T_output = T_input × Ratio × η_gearbox HP_output = HP_input × η_gearbox Where: η_gearbox = Gearbox efficiency (0.95–0.98 per stage)

Gearbox Service Factors

Driven Equipment Load Classification AGMA Service Factor Example
Centrifugal compressor Uniform load 1.00–1.25 Smooth torque, continuous operation
Centrifugal pump Moderate shock 1.25–1.50 Occasional transients
Reciprocating compressor Heavy shock 1.50–2.00 Pulsating torque, high starting load
Reciprocating pump Heavy shock 1.75–2.25 Severe pulsations

Gearbox Sizing Calculation

Rated Gearbox Torque: T_rated = (T_operating × SF_AGMA) / η_gearbox Where: T_operating = Operating torque at output shaft (lb·ft) SF_AGMA = Service factor from AGMA 6010 (see table above) η_gearbox = Gearbox mechanical efficiency (0.95–0.98) Thermal Rating Check: HP_thermal = k × (T_rated / 1000)^1.5 × (N_output / 100)^0.5 Where k depends on gearbox cooling method: k = 1.0 (natural convection) k = 1.5 (forced air cooling) k = 2.5 (oil cooling with heat exchanger) Verify: HP_operating < HP_thermal

Coupling Selection

Flexible couplings connect driver and driven shafts while accommodating misalignment, transmitting torque, and dampening vibrations.

Coupling Torque Rating: T_coupling = T_operating × SF_coupling Where: SF_coupling = Coupling service factor: - 1.5 (normal service, electric motor drive) - 2.0 (reciprocating equipment) - 2.5 (heavy shock loads) Misalignment Capacity: Parallel offset: 0.010–0.030 in (gear/grid couplings) Angular: 0.5°–1.5° (elastomeric couplings) Axial: ±0.125–0.250 in (typical) Torsional Stiffness: K_torsional = T / θ (lb·ft/rad) Where: T = Applied torque (lb·ft) θ = Angular deflection (radians) Soft couplings (elastomeric): K = 10³–10⁵ lb·ft/rad Stiff couplings (gear): K = 10⁶–10⁷ lb·ft/rad

Coupling Types Comparison

Coupling Type Torque Capacity Misalignment Damping Application
Gear (lubricated) Very high Moderate Low Large compressors, high torque
Grid High Moderate Moderate General purpose, pumps
Elastomeric Low-moderate High High Small pumps, vibration isolation
Disc pack Moderate Low Very low High-speed, precise alignment

5. Starting Torque & Power Factor

Electric motors draw high current during startup (locked rotor condition) and produce characteristic torque profiles as they accelerate to rated speed.

Motor Torque-Speed Curve

NEMA Design B motor torque-speed characteristic curve showing locked rotor torque (LRT) at 150% of full load torque at 0% speed, pull-up torque dip around 30% speed, breakdown torque peak at 200% near 80% speed, and full load torque at 100% near synchronous speed with 3% slip, including centrifugal load torque curve and shaded accelerating torque region
NEMA Design B induction motor torque-speed curve showing key operating points: LRT (150% min), pull-up (100% min), and breakdown torque (200% min). The shaded area represents accelerating torque available to bring load up to speed.
Torque Regions (NEMA Design B Motor): Locked Rotor Torque (LRT): 150% of FLT @ 0% speed Pull-up Torque: 100–150% FLT @ 50–80% speed Breakdown Torque (BDT): 200–300% FLT @ 80–90% speed Full-Load Torque (FLT): 100% @ rated speed Starting Current (Locked Rotor Amps): LRA = FLA × LRC Where: FLA = Full-load amps (nameplate) LRC = Locked rotor code multiplier (NEMA MG-1): - Code G: 5.0–5.6 × FLA - Code H: 5.6–6.3 × FLA - Code J: 6.3–7.1 × FLA - Code K: 7.1–8.0 × FLA - Code L: 8.0–9.0 × FLA Typical medium motors (50-500 HP): 6–7 × FLA

Starting Methods Comparison

Starting Method Starting Current Starting Torque Cost Application
Direct-on-line (DOL) 600–700% FLA 150–200% FLT Low Small motors, strong grid
Star-delta (Y-Δ) 200–250% FLA 50–60% FLT Low-moderate Light-load starts, Europe
Autotransformer 300–400% FLA 60–80% FLT Moderate Medium motors, limited grid
Soft starter (VFD) 200–400% FLA Variable, 50–100% FLT High Large motors, controlled ramp
Variable frequency drive 100–150% FLA 150% FLT (constant) Highest Variable speed, precise control

Power Factor and Reactive Power

AC power triangle diagram showing right triangle with horizontal leg P equals real power 80 kW in blue doing useful work, vertical leg Q equals reactive power 60 kVAR in red for magnetizing current, hypotenuse S equals apparent power 100 kVA in green as total power drawn, angle phi for power factor angle with PF equals 0.80 lagging, and equations S squared equals P squared plus Q squared
AC power triangle illustrating the relationship between real power (kW), reactive power (kVAR), and apparent power (kVA). Low power factor increases apparent power and current draw for the same useful work.
Power Factor Definition: PF = cos(φ) = P / S Where: P = Real power (kW) - does actual work S = Apparent power (kVA) - total power drawn φ = Phase angle between voltage and current Power Triangle: S² = P² + Q² Where: Q = Reactive power (kVAR) - magnetizing current Motor Power Factor vs Load: PF(load) ≈ PF_rated × (Load% / 100)^0.5 At 100% load: PF = 0.85–0.92 (typical) At 75% load: PF ≈ 0.86 × (0.75)^0.5 = 0.75 At 50% load: PF ≈ 0.86 × (0.50)^0.5 = 0.61 At 25% load: PF ≈ 0.86 × (0.25)^0.5 = 0.43 Low PF at light loads → poor efficiency, high reactive current

Motor Efficiency vs Load

Load (%) Efficiency (Premium Motor) Power Factor kW Input (100 HP motor)
25% 91.0% 0.55 20.5 kW
50% 94.5% 0.70 39.5 kW
75% 95.5% 0.82 58.5 kW
100% 95.0% 0.88 78.5 kW
115% (SF) 94.0% 0.89 91.0 kW

Voltage Drop During Starting

System Voltage Drop: ΔV% = (LRA / SC_available) × 100% Where: LRA = Locked rotor amps (starting current) SC_available = System short-circuit current capacity (amps) Acceptable limits: ΔV < 10% (large utility grid) ΔV < 15% (weak grid or remote location) ΔV < 5% (sensitive equipment on same bus) Example: 500 HP motor: FLA = 570 A @ 460V LRA = 6.5 × 570 = 3705 A System SC capacity = 25,000 A ΔV% = (3705 / 25000) × 100% = 14.8% Result: May require soft starter or larger transformer

Practical Considerations

  • Motor acceleration time: Typically 5–15 seconds for centrifugal loads; WK² (inertia) of driven equipment affects acceleration
  • Thermal limits: Number of starts per hour limited by motor thermal capacity (typically 2–3 starts/hour for large motors)
  • VFD benefits: Reduced starting current, adjustable speed, energy savings at partial load, but adds harmonics and requires motor insulation rating
  • Power factor correction: Capacitor banks improve PF but must be sized to avoid resonance; disconnect during starting to prevent voltage spike
Starting current impact: A 500 HP motor drawing 6.5 × FLA during startup requires 3700 A inrush current. This creates voltage sag affecting other equipment and requires proper transformer sizing, cable selection, and protective relay coordination. Soft starters or VFDs reduce starting current to 2–4 × FLA.