1. Fire Protection Philosophy
Fire water systems in gas plants and refineries serve as a critical layer of defense against hydrocarbon fires. The primary objectives are to cool equipment exposed to fire, prevent escalation to adjacent units, and provide manual firefighting capability.
Protection Objectives
Equipment cooling
Prevent failure
Water spray keeps steel below critical temperature (~1,000°F) to prevent loss of containment.
Exposure protection
Limit escalation
Cool adjacent equipment not yet involved in fire to prevent cascading failures.
Hose streams
Manual response
Provide water for firefighters to apply manually where fixed systems do not reach.
Fire control
Area containment
Contain fire to single process area and prevent plant-wide propagation.
Design Basis Fire Scenario
The fire water system is designed for the worst-case single fire event, not all areas simultaneously. Key assumptions include:
- Fire type: Pool fire from spilled hydrocarbons (most common in process facilities)
- Fire zone: Largest single fire area or scenario as defined by facility layout and hazard analysis
- Simultaneous demand: All equipment within the fire zone plus hose streams for adjacent areas
- Duration: Minimum 4 hours of continuous water supply per NFPA
2. NFPA Standards & Requirements
Multiple NFPA and API standards govern fire water system design for process facilities. Understanding the applicable standard for each equipment type is essential for defensible design.
Governing Standards
| Standard | Scope | Key Requirements |
|---|---|---|
| NFPA 15 | Water Spray Fixed Systems | Application densities, system design, nozzle selection |
| NFPA 30 | Flammable Liquids Code | Storage tank protection, spacing, containment |
| NFPA 20 | Stationary Fire Pumps | Pump selection, testing, reliability requirements |
| API 2510 | LPG Installations | LPG sphere/vessel protection, water spray rates |
| API 2030 | Water Spray Systems | Application of water spray for fire protection |
| GPSA Ch 18 | Safety & Relief | Gas plant fire protection guidelines |
NFPA 15 Application Densities
| Application | Density (gpm/ft²) | Reference |
|---|---|---|
| Vessel/tank cooling | 0.25 | NFPA 15 Table 5.3.2.4 |
| Exposure protection | 0.25 | NFPA 15 Table 5.3.2.4 |
| Structural steel protection | 0.10 | NFPA 15 Table 5.3.2.4 |
| Electrical transformers | 0.25 | NFPA 15 Table 5.3.2.4 |
| Cable trays | 0.30 | NFPA 15 Table 5.3.2.4 |
| Conveyor belts | 0.25 | NFPA 15 Table 5.3.2.4 |
25-ft height limit: Per NFPA 15, only surfaces within 25 ft above grade level are considered exposed to fire and require water spray protection. Surfaces above this elevation are generally above the expected flame height of a pool fire and do not require cooling.
Identify fire zones. Divide the facility into fire zones based on process areas, equipment spacing, and drainage boundaries.
List protected equipment. Identify all equipment within each zone requiring water spray protection.
Calculate wetted areas. Compute the exposed surface area for each equipment item within the 25-ft zone.
Sum demands. Add all cooling demands within the worst-case fire zone plus hose stream allowance.
3. Wetted Area Calculations
The wetted area is the surface area of equipment exposed to fire that requires water spray cooling. The calculation method depends on equipment geometry and orientation.
Horizontal Vessel
Vertical Vessel
Atmospheric Storage Tank
Sphere
Pipe Rack
Example: Horizontal Vessel
Given: 8 ft diameter x 40 ft long horizontal vessel, below 25 ft grade
Step 1: Shell area
Step 2: Head area (2 half-heads)
Step 3: Total wetted area
Step 4: Water demand
4. Deluge System Design
Deluge systems are open-head water spray systems that activate simultaneously when a fire is detected. They provide immediate, uniform water coverage over the protected equipment.
System Components
Deluge valve
System control
Normally closed valve that opens on fire signal, releasing water to all spray nozzles simultaneously.
Spray nozzles
Water distribution
Open-type nozzles sized for required density. Typical K-factors: 5.6, 8.0, 11.2, 14.0.
Detection
Fire sensing
Fusible links, heat detectors, or flame detectors trigger the deluge valve.
Piping
Distribution
Dry piping from deluge valve to nozzles. Sized for hydraulic balance and velocity limits.
Deluge Valve Sizing
| Flow Range (gpm) | Valve Size | Typical Application |
|---|---|---|
| ≤ 100 | 2" | Small vessels, instrument air compressors |
| 100 - 250 | 3" | Medium vessels, heat exchangers |
| 250 - 500 | 4" | Large vessels, small tanks |
| 500 - 1,000 | 6" | Large tanks, multiple vessels |
| 1,000 - 2,000 | 8" | Spheres, large equipment groups |
| 2,000 - 3,500 | 10" | Large spheres, tank farms |
| > 3,500 | 12" or multiple | Multiple zones required |
Nozzle Selection
Spray nozzles are selected to provide uniform coverage at the required application density. Key considerations:
- Spray angle: 120-180 degrees for full coverage
- K-factor: Relates flow to pressure: Q = K x sqrt(P)
- Spacing: Maximum 10 ft between nozzles for vessels; 12 ft for structural steel
- Minimum pressure: 30-35 psi at most remote nozzle for adequate spray pattern
- Orientation: Nozzles aimed at equipment surface, not at air space
5. Fire Pump Selection
Fire pumps must deliver the total fire water demand at adequate pressure to the most hydraulically remote point in the system. NFPA 20 governs pump selection, testing, and reliability requirements.
Pump Capacity
Total Dynamic Head (TDH)
TDH is the total pressure the pump must overcome, including:
| Component | Typical Range (psi) | Notes |
|---|---|---|
| Nozzle pressure | 30 - 75 | Minimum 30 psi for adequate spray pattern |
| Friction loss (piping) | 20 - 50 | Depends on pipe size, length, and flow rate |
| Elevation head | 10 - 50 | Height from pump to highest nozzle |
| Fitting/valve losses | 10 - 25 | Valves, elbows, tees in distribution |
| Typical Total TDH | 125 - 175 | 150 psi is common design basis |
Pump Types for Fire Service
Electric motor driven
Primary pump
Centrifugal pump with electric motor. Requires reliable power supply or emergency generator.
Diesel engine driven
Backup pump
Independent of electrical supply. Auto-starts on pressure drop in fire main. NFPA 20 requires weekly test runs.
Jockey pump
Pressure maintenance
Small pump to maintain system pressure and compensate for minor leaks. Prevents unnecessary main pump starts.
Redundancy requirement: NFPA 20 and most facility standards require at least two fire pumps, each capable of delivering 100% of the design demand. Typically one electric-driven and one diesel-driven pump are provided for maximum reliability.
Example: Pump Sizing
Given: Total demand = 3,000 gpm, TDH = 150 psi
6. Water Storage Design
Fire water storage must hold sufficient volume to sustain the design fire water demand for the required duration without replenishment.
Storage Volume Calculation
Typical Storage Requirements
| Facility Type | Typical Demand (gpm) | Duration (hrs) | Storage (gallons) |
|---|---|---|---|
| Small compressor station | 1,000 - 2,000 | 4 | 240,000 - 480,000 |
| Gas processing plant | 3,000 - 5,000 | 4 | 720,000 - 1,200,000 |
| NGL fractionation plant | 4,000 - 8,000 | 4 | 960,000 - 1,920,000 |
| LPG storage facility | 3,000 - 6,000 | 4 - 6 | 720,000 - 2,160,000 |
| Refinery unit | 5,000 - 15,000 | 4 - 8 | 1,200,000 - 7,200,000 |
Storage Tank Design Considerations
- Tank type: Atmospheric storage (API 650), typically ground-level or elevated
- Minimum volume: Dedicated fire water volume must not be shared with process water
- Replenishment: Makeup water system to refill after fire event (not credited for initial supply)
- Location: Outside process areas, protected from fire exposure, accessible to fire pumps
- Freeze protection: In cold climates, heating or recirculation may be required
- Water quality: Treated to prevent biological growth, corrosion, and nozzle plugging
Fire Water Ring Main
Fire water is typically distributed through a ring main (looped piping) around the facility. The ring main ensures water can reach any point from two directions, providing redundancy if a section is damaged. Ring main sizing is typically 10-12 inch diameter for gas plants, with 6-8 inch lateral branches to individual deluge zones.
References:
• NFPA 24 - Installation of Private Fire Service Mains
• API 2510 - Section 7.4 - Water Supply Distribution
References
- NFPA 15 - Standard for Water Spray Fixed Systems for Fire Protection
- NFPA 20 - Standard for the Installation of Stationary Pumps for Fire Protection
- NFPA 22 - Standard for Water Tanks for Private Fire Protection
- NFPA 24 - Standard for the Installation of Private Fire Service Mains
- NFPA 30 - Flammable and Combustible Liquids Code
- API 2510 - Design and Construction of LPG Installations
- API 2030 - Application of Water Spray Systems for Fire Protection
- GPSA Engineering Data Book, Chapter 18 - Safety, Relief, and Environmental
Ready to use the calculator?
→ Launch Fire Water Demand Calculator