Fire Case Relief

Fire Case Relief: API 521 Engineering Fundamentals

Size relief for pool fire exposure with defensible wetted area, heat input, and capacity calculations aligned to API 521/520.

Exposure height

25 ft zone

Wetted area limited to 25 ft above the base of the fire per API 521.

Heat input

Q = C·A^0.82

C depends on drainage/insulation credit.

Accumulation

21% over MAWP

Fire case relieving pressure per API 520.

Use this when you need to:

  • Screen PSV capacity for pool fire exposure.
  • Document wetted area/heat input assumptions.
  • Compare insulation or water spray credits.

1. Fire Case Principles

Fire exposure can cause rapid pressure rise in vessels containing liquids that vaporize when heated. Relief devices must handle the vapor generation rate to prevent vessel rupture.

Fire Case Scenario

Heat source

Pool fire

Assume spill-fed fire around vessel; flame height ~25–30 ft.

Exposure time

Until inventory gone

No credit for firefighting unless fully justified.

Relief driver

Vapor generation

Boil-off from wetted area drives relief load; liquid-only cases are rare.

Spacing

25 ft zone

Only wetted area ≤25 ft above the base of the fire is considered fire-exposed.

Governing Standards

Standard Scope
API 521 Pressure-relieving and depressuring systems (fire case methodology)
API 520 Part I Relief device sizing equations
NFPA 30 Flammable liquids storage
29 CFR 1910.106 OSHA flammable liquid requirements

2. Wetted Area Calculation

API 521 4.4.13.2.2: wetted area is the part of the vessel surface in contact with liquid that is 7.6 m (25 ft) or less above the base of the pool fire. The base of the pool fire is usually grade, but it can be any level at which a substantial spill or pool fire could be sustained. Table 4 says how much liquid to assume for each class of vessel.

API 521 Table 4: Liquid Inventory by Vessel Class

Class of vesselLiquid inventory to use
Liquid-full, such as treatersAll, up to 25 ft
Surge drums, knockout drums, process vesselsNormal operating level, up to 25 ft
Fractionating columnsNormal level in the bottom plus the liquid holdup from all trays dumped to it (and the reboiler level if it is integral to the column), total wetted surface up to 25 ft
Working storageMaximum inventory level, up to 25 ft; portions in contact with foundations or the ground are normally excluded (low-pressure tanks, below 15 psig: see API 2000)
Spheres and spheroidsUp to the maximum horizontal diameter or up to 25 ft, whichever is greater

Also, vessel heads protected by support skirts with limited ventilation are normally not included, and the user shall specify whether the wetted area of connected piping is included (the calculator does not add it).

Horizontal Vessel

Wetted area (horizontal cylinder shell): A_w,shell = L × 2r × arccos((r-h)/r) Equivalent form (θ in degrees): A_w,shell ≈ L × π × D × (θ/360) Add head wetted area (one head per end): • 2:1 elliptical: ≈ A_head,full × (h/D) • Hemispherical: = 2πr² × (h/D) • Flat: = circular segment area at depth h Where: A_w = Wetted area (ft²) L = Vessel length (tan-to-tan) (ft) D = Vessel diameter (ft) r = Radius (ft) h = Wetted depth (ft): the liquid depth or 25 ft minus the elevation of the vessel's lowest point above grade, whichever is less θ = Central angle subtended by the wetted arc (= 2·arccos((r-h)/r), in degrees) A vessel with its lowest point E feet above grade exposes only the depth up to 25 − E; a vessel partly below grade exposes only the depth above grade.

Vertical Vessel

Wetted area (vertical cylinder), each part limited to between grade and 25 ft above the base of the fire: A_w = A_bottom_head + π × D × h_shell + A_top_head (liquid-full vessels only) h_shell = shell height that is wet and between grade and 25 ft above the base of the fire A_bottom_head (excluded for a skirted head, and for a storage tank bottom in contact with the ground): • Flat: A = π × D²/4 • 2:1 elliptical: A ≈ 1.084 × D² ≈ 1.38 × π × r² (a head 10 ft in diameter: 108.4 ft²) • Hemispherical: A = 2 × π × r² (a partial head, where the 25 ft limit or grade crosses the head, is integrated over the exposed part) Example: 10 ft diameter, 30 ft tangent to tangent, 2:1 elliptical heads, liquid-full, at grade: A_w = 108.4 + π × 10 × 22.5 = 815 ft² (the bottom head is 2.5 ft deep, so the shell is wetted from 2.5 to 25 ft)

Sphere

Wetted area (sphere or spheroid), API 521 Table 4: A_w = π × D × h_wet (area of a spherical zone of depth h_wet is 2πr h_wet) h_wet = liquid depth, up to the greater of the equator (r) and 25 ft minus the elevation of the sphere's lowest point The whole bottom hemisphere is therefore always included when it is wetted, even if the equator is higher than 25 ft: pool fire flames can follow the underside of the sphere. For a 40 ft sphere that is full, at grade: A_w = π × 40 × 25 = 3,142 ft²; with its lowest point 10 ft above grade: π × 40 × 20 = 2,513 ft² (bottom hemisphere).
25-ft rule: Only liquid-wetted area within 25 ft of the base of the fire is counted, measured from grade, not from the bottom of the vessel. For an elevated vessel the allowed depth is smaller; for a sphere the bottom hemisphere is the minimum.

3. Heat Input Equations

API 521 provides equations for heat absorption based on wetted area and drainage/firefighting provisions.

Heat Input Equations

API 521 Heat Input (Pool Fire): Q = C × F × A^0.82 (The A^0.82 form applies across the full wetted-area range — there is no separate linear small-vessel branch; a linear Q = C·F·A over-predicts ~2.6× at A = 200 ft² and is non-standard.) Heat flux constant C: C = 21,000 BTU/(hr·ft^1.64) — Eq. (7), adequate drainage & firefighting C = 34,500 BTU/(hr·ft^1.64) — Eq. (8), inadequate drainage Where: Q = Heat absorption rate (BTU/hr) F = Environment factor (see table below) A = Wetted area (ft²)
Adequate drainage (API 521 §4.4.13.2.4.2): API 521 leaves the definition to the user; drainage should carry flammable liquids and firefighting water away from the vessel, and prompt firefighting should be available (example criteria are given in API 2510). Typical practice: a slope of at least 1% away from the vessel and drainage capacity for the spill. If adequate drainage and firefighting do not exist, use C = 34,500 (Eq. 8).

Environmental Factor (F)

Condition F Factor Notes
Bare vessel (no insulation) 1.0 Default assumption
Water application facilities on a bare vessel 1.0 No credit: Table 5 gives 1.0 (note e: F does not apply to uninsulated vessels)
Depressurizing and emptying facilities 1.0 No credit in the heat input equation; depressuring is a separate protection method (API 521 4.6)
Fireproof insulation (single layer) F = k(1660 − Tf) / (21,000 δ) API 521 Eq. 18, k in Btu·in/h·ft²·°F, δ in inches, Tf = contents temperature at relieving conditions; use 1.0 if the result exceeds 1.0. Insulation must stay in place in a fire (1660°F, hose stream resistant)
Insulation (conductance 4 BTU/hr·ft²·°F) 0.3 Table 5 value
Insulation (conductance 2 BTU/hr·ft²·°F) 0.15 Better insulation performance
Insulation (conductance 1 BTU/hr·ft²·°F) 0.075 Table 5 value; further values 0.05 (0.67), 0.0376 (0.5), 0.03 (0.4), 0.026 (0.33)
Earth-covered storage 0.03 Mounded tanks (below grade storage is 0.00)

Reference: API 521 Table 5 — Environment factors for fire exposure calculations.

⚠ Insulation requirements: To claim F < 1.0, insulation must be fireproof (calcium silicate, mineral wool with stainless steel jacket). Standard weatherproofing does not qualify.

01

Set exposure assumptions. Define drainage/spacing and insulation to pick the correct C and F factors.

02

Compute Q. Use the API 521 equation with wetted area capped at 25 ft.

03

Document credit. If claiming F < 1.0 or water spray, capture justification in the relief summary.

Jet Fire and Storage Tank Notes

Storage tanks

API 521 4.4.13.2.4.2 Eq. (7) and (8) apply to vessels containing liquids, storage vessels included, with the Table 4 wetted area (working storage: maximum inventory level up to 25 ft; ground contact excluded). The calculator uses them for the storage tank type. Atmospheric and low-pressure tanks (below 15 psig) are covered by API 2000, which has its own heat input table by wetted area; use the Tank Vent Sizing calculator for those.

Jet fire

API 521 4.4.13.1 gives 100 to 400 kW/m² (31,700 to 126,800 Btu/h·ft²) as the typical jet fire range, and Table A.5 gives recommended absorbed fluxes where other data are not available: large jet (leak above 2 kg/s) surface average 85 kW/m² (26,945 Btu/h·ft²) and local peak 290 kW/m² (91,930); small jet local peak 210 kW/m² (66,570). The surface average flux gives the heat input to the process fluid (A.3.2); the local peak flux gives the localized wall temperature. The calculator multiplies the chosen flux by the wetted area and applies no environment factor, because Table 5 belongs to the pool fire equations and insulation may not survive a jet.

PRDs and jet fire: API 521 4.4.13.4 says protection from jet fire is typically addressed by means other than pressure relief (leak prevention, passive fire protection, depressuring), because failure comes from localized overheating of the wall, often before the vessel pressure rises.

4. Relief Load Calculation

The relief load equals the vapor generation rate from heat input divided by latent heat of vaporization.

Vapor generation rate: W = Q / λ Where: W = Relief rate (lb/hr) Q = Heat input (BTU/hr) λ = Latent heat of vaporization at relief conditions (BTU/lb)

Latent Heat Values

Fluid Condition λ (BTU/lb)
Water 100 psig (338°F) 881
Water 250 psig (406°F) 820
Propane 100 psig (saturation) 150
Propane 250 psig (saturation) 110
Butane 100 psig (saturation) 130
Pentane 50 psig (saturation) 140
Crude oil (light) Atmospheric 100–120
Important: Latent heat decreases as pressure increases toward the critical point. Always use λ at the relieving pressure (set pressure + accumulation), not normal operating conditions. Use process simulation for accurate values.

Example Calculation

Given: Horizontal propane vessel, 10 ft diameter × 40 ft long, 80% full, bare vessel, adequate drainage

Step 1: Wetted area

80% full → θ ≈ 253° of circumference wetted A_w = 40 × π × 10 × (253/360) + 2 × 1.084 × 10² × 0.8 A_w = 883 + 173 = 1,056 ft² (2:1 ellipsoidal heads, 1.084·D² each)

Step 2: Heat input

Q = 21,000 × 1.0 × (1,056)^0.82 Q = 21,000 × 301.6 = 6,333,600 BTU/hr

Step 3: Relief load

λ = 130 BTU/lb (propane at relief pressure) W = 6,333,600 / 130 = 48,720 lb/hr

5. Design Considerations

Relief Device Sizing

Use API 520 gas sizing equation with fire case relief load:

A = W / (C × K_d × P₁ × K_b × √(M/TZ)) Where: A = Required orifice area (in²) W = Fire relief load (lb/hr) C = Gas constant (depends on k ratio) K_d = Discharge coefficient (0.975 typical) P₁ = Relief pressure (psia) K_b = Backpressure correction M = Molecular weight T = Temperature (°R) Z = Compressibility factor

Relief Pressure

Parameter Fire Case Allowance
Set pressure ≤ MAWP
Accumulation (fire only) 21% above MAWP
Relieving pressure 1.21 × MAWP

💡 Design Margin Assurance

Relieving pressure of 121% MAWP is permitted for fire cases per API 520 Part I, Table 6. Vessel integrity is assured since ASME Section VIII requires hydrostatic testing to 150% MAWP (1.5 × design pressure), providing adequate margin above fire-case relieving conditions.

References:
• API 520 Part I, 10th Ed., Table 6 – Pressure Limits for Pressure-Relief Devices
• ASME BPVC Section VIII, Div. 1, UG-99 – Hydrostatic Testing Requirements

Alternative Protection Methods

  • Depressuring: Automatic blowdown to reduce pressure below failure threshold (API 521 Section 4.6, Vapor Depressuring)
  • Water spray: Deluge helps keep the wall cool but API 521 Table 5 gives no reduction in F for it on a bare vessel (F = 1.0); size the relief device without credit (API 521 4.4.13.2.6.2)
  • Fireproofing: Concrete or intumescent coating extends survival time
  • Remote location: Adequate spacing reduces fire exposure probability

References

  • API 521 – Pressure-Relieving and Depressuring Systems, 7th Edition
  • API 520 Part I – Sizing, Selection, and Installation of PRDs
  • API 2000 – Venting Atmospheric and Low-Pressure Storage Tanks
  • NFPA 30 – Flammable and Combustible Liquids Code

Frequently Asked Questions

What is fire relief valve sizing?

Fire relief valve sizing involves calculating the required relief capacity based on API 521 fire case methods, including wetted area determination and heat input calculations.

What standard is used for fire case relief calculations?

API 521 is the primary standard used for fire case calculations, covering wetted area, heat input, and relief valve sizing for fire exposure scenarios.

What is wetted area in fire relief calculations?

Wetted area is the vessel surface area in contact with liquid that is exposed to fire, used to calculate heat absorption and the required relief rate per API 521.