1. Fire Case Principles
Fire exposure can cause rapid pressure rise in vessels containing liquids that vaporize when heated. Relief devices must handle the vapor generation rate to prevent vessel rupture.
Fire Case Scenario
Heat source
Pool fire
Assume spill-fed fire around vessel; flame height ~25–30 ft.
Exposure time
Until inventory gone
No credit for firefighting unless fully justified.
Relief driver
Vapor generation
Boil-off from wetted area drives relief load; liquid-only cases are rare.
Spacing
25 ft zone
Only wetted area ≤25 ft above the base of the fire is considered fire-exposed.
Governing Standards
| Standard | Scope |
|---|---|
| API 521 | Pressure-relieving and depressuring systems (fire case methodology) |
| API 520 Part I | Relief device sizing equations |
| NFPA 30 | Flammable liquids storage |
| 29 CFR 1910.106 | OSHA flammable liquid requirements |
2. Wetted Area Calculation
API 521 4.4.13.2.2: wetted area is the part of the vessel surface in contact with liquid that is 7.6 m (25 ft) or less above the base of the pool fire. The base of the pool fire is usually grade, but it can be any level at which a substantial spill or pool fire could be sustained. Table 4 says how much liquid to assume for each class of vessel.
API 521 Table 4: Liquid Inventory by Vessel Class
| Class of vessel | Liquid inventory to use |
|---|---|
| Liquid-full, such as treaters | All, up to 25 ft |
| Surge drums, knockout drums, process vessels | Normal operating level, up to 25 ft |
| Fractionating columns | Normal level in the bottom plus the liquid holdup from all trays dumped to it (and the reboiler level if it is integral to the column), total wetted surface up to 25 ft |
| Working storage | Maximum inventory level, up to 25 ft; portions in contact with foundations or the ground are normally excluded (low-pressure tanks, below 15 psig: see API 2000) |
| Spheres and spheroids | Up to the maximum horizontal diameter or up to 25 ft, whichever is greater |
Also, vessel heads protected by support skirts with limited ventilation are normally not included, and the user shall specify whether the wetted area of connected piping is included (the calculator does not add it).
Horizontal Vessel
Vertical Vessel
Sphere
3. Heat Input Equations
API 521 provides equations for heat absorption based on wetted area and drainage/firefighting provisions.
Heat Input Equations
Environmental Factor (F)
| Condition | F Factor | Notes |
|---|---|---|
| Bare vessel (no insulation) | 1.0 | Default assumption |
| Water application facilities on a bare vessel | 1.0 | No credit: Table 5 gives 1.0 (note e: F does not apply to uninsulated vessels) |
| Depressurizing and emptying facilities | 1.0 | No credit in the heat input equation; depressuring is a separate protection method (API 521 4.6) |
| Fireproof insulation (single layer) | F = k(1660 − Tf) / (21,000 δ) | API 521 Eq. 18, k in Btu·in/h·ft²·°F, δ in inches, Tf = contents temperature at relieving conditions; use 1.0 if the result exceeds 1.0. Insulation must stay in place in a fire (1660°F, hose stream resistant) |
| Insulation (conductance 4 BTU/hr·ft²·°F) | 0.3 | Table 5 value |
| Insulation (conductance 2 BTU/hr·ft²·°F) | 0.15 | Better insulation performance |
| Insulation (conductance 1 BTU/hr·ft²·°F) | 0.075 | Table 5 value; further values 0.05 (0.67), 0.0376 (0.5), 0.03 (0.4), 0.026 (0.33) |
| Earth-covered storage | 0.03 | Mounded tanks (below grade storage is 0.00) |
Reference: API 521 Table 5 — Environment factors for fire exposure calculations.
⚠ Insulation requirements: To claim F < 1.0, insulation must be fireproof (calcium silicate, mineral wool with stainless steel jacket). Standard weatherproofing does not qualify.
Set exposure assumptions. Define drainage/spacing and insulation to pick the correct C and F factors.
Compute Q. Use the API 521 equation with wetted area capped at 25 ft.
Document credit. If claiming F < 1.0 or water spray, capture justification in the relief summary.
Jet Fire and Storage Tank Notes
Storage tanks
API 521 4.4.13.2.4.2 Eq. (7) and (8) apply to vessels containing liquids, storage vessels included, with the Table 4 wetted area (working storage: maximum inventory level up to 25 ft; ground contact excluded). The calculator uses them for the storage tank type. Atmospheric and low-pressure tanks (below 15 psig) are covered by API 2000, which has its own heat input table by wetted area; use the Tank Vent Sizing calculator for those.
Jet fire
API 521 4.4.13.1 gives 100 to 400 kW/m² (31,700 to 126,800 Btu/h·ft²) as the typical jet fire range, and Table A.5 gives recommended absorbed fluxes where other data are not available: large jet (leak above 2 kg/s) surface average 85 kW/m² (26,945 Btu/h·ft²) and local peak 290 kW/m² (91,930); small jet local peak 210 kW/m² (66,570). The surface average flux gives the heat input to the process fluid (A.3.2); the local peak flux gives the localized wall temperature. The calculator multiplies the chosen flux by the wetted area and applies no environment factor, because Table 5 belongs to the pool fire equations and insulation may not survive a jet.
4. Relief Load Calculation
The relief load equals the vapor generation rate from heat input divided by latent heat of vaporization.
Latent Heat Values
| Fluid | Condition | λ (BTU/lb) |
|---|---|---|
| Water | 100 psig (338°F) | 881 |
| Water | 250 psig (406°F) | 820 |
| Propane | 100 psig (saturation) | 150 |
| Propane | 250 psig (saturation) | 110 |
| Butane | 100 psig (saturation) | 130 |
| Pentane | 50 psig (saturation) | 140 |
| Crude oil (light) | Atmospheric | 100–120 |
Example Calculation
Given: Horizontal propane vessel, 10 ft diameter × 40 ft long, 80% full, bare vessel, adequate drainage
Step 1: Wetted area
Step 2: Heat input
Step 3: Relief load
5. Design Considerations
Relief Device Sizing
Use API 520 gas sizing equation with fire case relief load:
Relief Pressure
| Parameter | Fire Case Allowance |
|---|---|
| Set pressure | ≤ MAWP |
| Accumulation (fire only) | 21% above MAWP |
| Relieving pressure | 1.21 × MAWP |
💡 Design Margin Assurance
Relieving pressure of 121% MAWP is permitted for fire cases per API 520 Part I, Table 6. Vessel integrity is assured since ASME Section VIII requires hydrostatic testing to 150% MAWP (1.5 × design pressure), providing adequate margin above fire-case relieving conditions.
References:
• API 520 Part I, 10th Ed., Table 6 – Pressure Limits for Pressure-Relief Devices
• ASME BPVC Section VIII, Div. 1, UG-99 – Hydrostatic Testing Requirements
Alternative Protection Methods
- Depressuring: Automatic blowdown to reduce pressure below failure threshold (API 521 Section 4.6, Vapor Depressuring)
- Water spray: Deluge helps keep the wall cool but API 521 Table 5 gives no reduction in F for it on a bare vessel (F = 1.0); size the relief device without credit (API 521 4.4.13.2.6.2)
- Fireproofing: Concrete or intumescent coating extends survival time
- Remote location: Adequate spacing reduces fire exposure probability
References
- API 521 – Pressure-Relieving and Depressuring Systems, 7th Edition
- API 520 Part I – Sizing, Selection, and Installation of PRDs
- API 2000 – Venting Atmospheric and Low-Pressure Storage Tanks
- NFPA 30 – Flammable and Combustible Liquids Code
Ready to use the calculator?
→ Launch Calculator