Permitting & Compliance

Emergency Shutdown (ESD) System Design

Emergency shutdown systems protect personnel and equipment by isolating the station from the pipeline and venting high-pressure gas during emergencies. This guide covers ESD design requirements per DOT 49 CFR 192, valve logic, and fail-safe principles.

Actuation Points

Minimum 2

Manual ESD stations required outside gas area, near exits.

Valve Response

10 seconds

Control gas line sized to operate all valves within 10 seconds.

Battery Backup

2 hours min

Protection system power supply battery backup requirement.

Related

Station Layout

Equipment spacing and ESD actuation point placement requirements.

View Guide →

1. Introduction

The plant protection system provides tiered responses to successive levels of hazard. The most significant hazards (fire) trigger a full plant Emergency Shutdown (ESD). Less significant hazards may limit operation to a single building or unit without full station isolation.

Regulatory Framework

  • 49 CFR Part 192: Transportation of Natural Gas by Pipeline - Minimum Federal Safety Standards
  • NEC (NFPA 70): National Electrical Code requirements for installations
  • State/Local regulations: Municipal, state, and federal regulations as applicable

Applicability

ESD functions shall be implemented for all compressor stations of 1,000 installed horsepower or more. Unattended field compressor stations of 1,000 HP or less are exempt from some requirements.

Protection Hierarchy: The protection system is segregated into functions based on maintaining operation during less serious hazards. Full ESD is reserved for the most significant hazards, while Fuel Gas Shutdown (FGS) limits response to a single building.

Protection System Levels

Level Response Scope
Plant ESD Full isolation and blowdown Entire station
Fuel Gas Shutdown (FGS) Block/vent fuel, unit stops Single building
Unit Shutdown Individual unit stop Single compressor
Alarm Only Annunciation, time-limited Monitoring point

2. Plant ESD System

The Plant ESD System isolates the compressor station from the pipeline and vents the station yard high-pressure piping to atmosphere. It is the response dictated for the most significant hazard expected (fire).

ESD System Functions

  • Block gas out of the station (close side valves)
  • Blow down station piping to atmosphere
  • Shut down gas compressing equipment
  • De-energize electrical facilities in gas header area
  • Discharge gas at a location where it will not create a hazard

Pneumatic Control System

The ESD operates by directing high-pressure gas from a secure source into a pneumatic control line. The control line is pressurized to activate the ESD.

Component Requirement
Volume storage vessel Fed from highest pipeline pressure available
Control gas line size 2" nominal minimum
Valve actuation time All valves within 10 seconds
Valve operators Direct acting, no spring return required

Manual Control Stations

At least two manually operated pneumatic control stands shall exist to initiate the system by pressurizing the Control Gas line:

  • One located in a safe area accessible during fire near compressor building
  • Outside the gas area of the station
  • Near exit gates (fenced station) or emergency exits (unfenced)
  • Maximum 500 ft from station limits
  • Minimum 25 ft from compressor building
Plot plan showing ESD stations at opposite corners with 25 ft minimum from building, 500 ft maximum reach, escape routes from all exits, and redundant placement for personnel safety
ESD placement: Stations at opposite corners ensure personnel can reach shutdown from any location; 500 ft max from any point in building.

Valve Operations During ESD

Valve Type Action on ESD Actuation
Side valves (inlet/outlet) Close Direct from control gas line
Blow-off valves Open (vent to atmosphere) Direct from control gas line
Bypass valves Position as required May be electric (non-critical)
Direct Acting Valves: All operators shall be piped to admit control or power gas to position the valve for a safe blown-down condition without the use of spring return operators or pressure-maintained positioners.

Electric ESD Initiation

Two design principles are acceptable for electrically initiated ESD:

Option 1: Master ESD Circuit (Fail-Safe)

  • Normally energized solenoid control valve
  • Breaking the circuit activates ESD
  • Provides true fail-safe operation
  • Any wire break, power loss, or button press triggers ESD

Option 2: Supervised Circuit

  • Normally de-energized solenoid
  • Energizing the circuit activates ESD
  • Circuit continuity is monitored
  • Failures are annunciated without triggering ESD

Master ESD Circuit: When required, the Master ESD Circuit shall be routed through dedicated conduit. All conduit and fittings shall be dedicated to the circuit and shall not share any other circuits.

3. Fuel Gas Shutdown (FGS)

The Fuel Gas Shutdown is a response to a lesser hazard, limiting the response to a single building without requiring isolation and blowdown of the entire station yard piping.

FGS Components

Component Function
Fuel block valve Isolates fuel gas supply to building
Fuel vent valve Vents fuel piping to atmosphere
Unit controls Forces suction/discharge valves closed
Case vent Vents compressor cases
Electrical disconnect De-energizes non-essential circuits

FGS Operation

  • Fuel blocked and vented by pair of flow control valves
  • Solenoid control valve operates pilot to position block/vent valves
  • Pneumatic connection to ESD control gas line preferred
  • ESD activation also causes FGS
  • Block/vent valves shall not reposition when ESD control gas is de-pressurized

Unit Shutdown Methods

Stop Type Description Application
Emergency Stop Immediate shutdown, case vented Safety-critical situations
Fast Stop Rapid shutdown with case venting Lesser hazards (with vent provision)
Normal Stop Controlled shutdown sequence Routine operations

FGS vs. ESD Comparison

Feature ESD FGS
Scope Entire station Single building
Pipeline isolation Yes No
Yard piping blowdown Yes No
Fuel gas blocked Yes Yes (building only)
Units affected All Building units only

4. Detection Systems

A standard set of instrumentation shall be provided for compressor buildings to protect personnel and equipment. For unattended facilities, this includes flame detection, fire detection, and hazardous gas detection.

Required Detection Types

Detection Type Technology Purpose
Flame Detection UV/IR optical Detect oil fires at compressor base
Fire Detection High heat detectors Detect hot gases near roof
Gas Detection IR point or open path Detect hydrocarbon releases

Flame Detection

  • UV/IR combination detectors for reliability
  • Coverage of all locations around compressor engine base
  • Primary purpose: detect oil fires
  • Sufficient detectors to sense fire at any location

High Heat Detectors

  • Installed near roof to detect hot gas accumulation
  • Additional detectors in pits and basements with restricted airflow
  • Rate-of-rise or fixed temperature types

Hazardous Gas Detectors

Required in all compressor buildings:

Detector Type Application Conditions
Open path IR Large open areas Building arrangement allows effective use
Point IR Localized monitoring Temperature maintained within limits
Catalytic bead General purpose Clean atmosphere required

Detection Response Matrix

Detection Level 1 Response Level 2 Response
Flame detected FGS, alarm ESD (confirmed fire)
High heat Alarm, ventilation FGS (sustained)
Gas 20% LEL Alarm, ventilation
Gas 50% LEL FGS, unit stops ESD (automatic for offshore)
50% LEL Trigger: Per 49 CFR 192, when gas concentration reaches 50% or more of LEL in a building with ignition source, ESD must actuate automatically for offshore/inland water platforms. Class 1, Group D electrical equipment is not considered an ignition source.

5. Control Logic

A control system shall monitor instruments and provide control actions as needed. It shall include event recorder, annunciator, and operator interface functions.

Logic Implementation Options

  • Hardwired relay-based controls
  • Programmable Logic Controllers (PLCs)
  • Dedicated safety processors
  • Contact/button strings (simple systems)

Standard Functions Matrix

All new compressor buildings shall implement the standard protection matrix:

Function Type Notes
High Heat Detection Required With fault detection
Ventilation Control Required Start/stop capability
Electrically Initiated ESD Required With fault monitoring
Electrically Initiated FGS Required With fault monitoring
Manually Initiated ESD Required With fault monitoring
Manually Initiated FGS Optional With fault monitoring
Shunt Trip - Lights Required Non-essential circuits
Unit Emergency Stop Required Hard wired
Unit Fast Stop w/ Vent Required Hard wired
Fire Horn Required Enabled when attended
Blue Beacon Optional Visual alarm

Bypass and Testing

  • Functions may be bypassed for maintenance with permanently installed switches
  • All bypassed functions shall be annunciated
  • Bypasses shall be automatically recorded by event recorder
  • ESD and FGS test functions required

Monitoring Display Requirements

Protection system shall include dedicated monitoring display in a "safe" area:

  • Event logs and operator interface
  • At least two displays if merged with automation system
  • One display in designated safe area
  • Isolated communications circuit for safe area display
  • Battery backup and standby generator power

6. Power Supply

A dedicated power supply shall be provided for the protection system with battery backup to ensure operation during power outages.

Power Supply Requirements

Parameter Requirement
Battery backup (no generator) Minimum 2 hours
Battery backup (with generator) Minimum 20 minutes
Master ESD circuit power Dedicated feed, maximum reliability

Acceptable Power Supply Types

Type 1: DC Battery Bank

  • Large bank of DC batteries
  • Redundant DC chargers
  • Optional inverter for 120 VAC loads

Type 2: Commercial AC UPS

  • Commercial grade AC UPS
  • External bypass switch for rapid replacement
  • External distribution breakers

Type 3: Distributed Small Supplies

  • Multiple small DC supplies and AC inverters
  • Individual power to selected loads
  • Sized for load transfer after single supply failure
  • Redundancy through cross-connection capability

Conduit and Wiring

When Master ESD Circuit is required:

  • Route through dedicated conduit
  • All conduit and fittings dedicated to ESD circuit
  • No sharing with non-protection system circuits
  • Underground routing preferred
  • If through shared pillboxes: isolate with liquid tight (red color-coded)

Underground Routing: When routed underground, care shall be taken in placement to minimize the effect of adjacent activity. Dedicated underground routing is preferred.

7. Code Requirements

Applicable Codes & Standards

Code/Standard Scope
49 CFR Part 192 Gas transmission pipeline safety standards
NFPA 70 (NEC) Electrical installations
API RP 14C Analysis, design of safety systems (offshore)
IEC 61511 Safety instrumented systems
NFPA 72 Fire alarm and signaling code

49 CFR 192 ESD Requirements Summary

  • Required for stations >1,000 HP (except unattended field stations)
  • Must block gas and blow down station piping
  • Must discharge gas at safe location
  • Must shut down compressors, gas fires, and electrical (except emergency lighting and equipment protection circuits)
  • Operable from at least 2 locations outside gas area
  • Locations near exit gates/exits, within 500 ft of station

Automatic ESD Triggers (Offshore/Inland Waters)

Condition Station Type Action
Pressure = MAOP + 15% Unattended Automatic ESD
Uncontrolled fire on platform Unattended Automatic ESD
Uncontrolled fire in building In building Automatic ESD
Gas ≥ 50% LEL with ignition source In building Automatic ESD

Electrical Exceptions During ESD

The following may remain energized during ESD:

  • Emergency lighting: Required to assist personnel evacuation
  • Equipment protection: Circuits needed to protect equipment from damage

References

  • 49 CFR Part 192 – Transportation of Natural Gas by Pipeline (DOT/PHMSA)
  • NFPA 70 – National Electrical Code
  • NFPA 72 – National Fire Alarm and Signaling Code
  • API RP 14C – Analysis, Design, Installation of Basic Surface Safety Systems
  • Safety Instrumented Systems
  • API RP 500 – Classification of Locations for Electrical Installations