Permitting & Compliance

Electrical Area Classification

Class I Division 1 & Division 2 hazardous area classification for natural gas compressor stations and processing facilities per NEC 500, API RP 500, and API RP 505.

Natural Gas

Class I, Group D

Methane-based facilities classification per NEC 500.

Methane LEL

5% by Volume

Lower Explosive Limit for natural gas in air.

Auto-Ignition

580°C (1076°F)

Maximum surface temperature for T1 equipment.

1. Classification Overview

Electrical area classification is a method of analyzing and classifying the environment where flammable gases or vapors may be present, enabling the proper selection of electrical equipment to prevent ignition sources. In natural gas facilities, this classification is critical for personnel safety and regulatory compliance.

Classification Purpose

The primary purpose of area classification is to identify locations where flammable gas-air mixtures may exist and specify the type of electrical equipment and wiring methods that can be safely used in each location.

Governing Standards

Electrical area classification in the United States is governed by multiple standards that work together:

Standard Scope Application
NEC Article 500 Division System Traditional US classification method
NEC Article 505 Zone System IEC-based classification (optional in US)
API RP 500 Petroleum Facilities Refineries and chemical plants
API RP 505 Petroleum Facilities (Zone) Zone system for petroleum industry
NFPA 497 Classification Guidelines Recommended practice for classification

Class I Gases and Vapors

Natural gas facilities are classified as Class I locations because they handle flammable gases and vapors. Class I is further divided into groups based on the specific gases present:

Group Representative Gas Application
Group A Acetylene Welding operations
Group B Hydrogen Refineries, hydrogen plants
Group C Ethylene Petrochemical facilities
Group D Methane (Natural Gas) Gas processing, compressor stations

Natural Gas Classification

Natural gas facilities are typically classified as Class I, Group D locations. Methane, the primary component of natural gas, has a Lower Explosive Limit (LEL) of approximately 5% and Upper Explosive Limit (UEL) of approximately 15% by volume in air.

2. Division Classification System

The Division system (NEC Article 500) is the traditional classification method used in the United States. It divides hazardous areas into two divisions based on the likelihood of flammable atmospheres being present.

Classification Definition Probability
Division 1 Flammable concentrations exist under normal operating conditions Continuous or frequent
Division 2 Flammable concentrations exist only under abnormal conditions Abnormal/failure only
Non-Hazardous Flammable concentrations not expected Not anticipated

Key Distinction

The fundamental difference between Division 1 and Division 2 is the frequency and likelihood of a flammable atmosphere being present:

  • Division 1: Hazardous atmosphere expected during normal operations (e.g., inside a compressor building where seals may leak)
  • Division 2: Hazardous atmosphere only during equipment failure, maintenance, or abnormal conditions (e.g., outdoor areas near flanged connections)

Equipment Requirements

Division 1 areas require explosion-proof or intrinsically safe equipment. Division 2 areas may use less restrictive equipment types but still require protection against sparks and hot surfaces. Using Division 2-rated equipment in Division 1 areas is a code violation and serious safety hazard.

3. Division 1 Areas

Division 1 locations are areas where flammable gas-air mixtures may exist under normal operating conditions or where equipment failure could simultaneously release flammable materials and create an ignition source.

Typical Division 1 Locations

The following areas in natural gas facilities are typically classified as Division 1:

Compressor Buildings

The interior of compressor buildings housing gas compressors is classified Division 1 because compressor seals, packing, and connections may release gas during normal operation. This includes the entire enclosed space unless adequately ventilated and separated.

Location Reason for Division 1 Classification
Compressor buildings (interior) Seal leakage during normal operation
Fuel gas scrubber buildings Potential leakage from piping and vessels
Inadequately ventilated meter buildings Accumulation of leaked gas
Areas within 5 ft of relief valves/vents Designed release points
Pits, trenches, and sumps Gas accumulation in low points
Unventilated basements below grade Heavier-than-air vapors collect
Areas around open process vessels Continuous vapor release

Division 1 Extent

Standard Division 1 extents from various sources in natural gas facilities:

Source Horizontal Extent Vertical Extent
Relief valve discharge 5 ft radius To grade or 5 ft above
Vent openings 5 ft radius 5 ft above opening
Compressor seal area 3 ft radius Floor to 3 ft above
Sample points 3 ft radius 3 ft above point

Equipment Requirements for Division 1

  • Explosion-proof enclosures - Contain any internal explosion and prevent ignition of external atmosphere
  • Intrinsically safe circuits - Energy limited to prevent ignition
  • Purged and pressurized enclosures - Maintain positive pressure with clean air
  • Oil-immersed equipment - Arcing contacts submerged in oil

4. Division 2 Areas

Division 2 locations are areas where flammable gas-air mixtures are handled, processed, or used but are normally confined within closed containers or systems. Hazardous concentrations occur only during accidental rupture, breakdown, or abnormal operation.

Typical Division 2 Locations

Location Reason for Division 2 Classification
5-15 ft from Division 1 sources Transition zone from release points
Within 25 ft of piping with flanges/valves Potential leak points (gasket failure)
Within 100 ft horizontal of Division 1 Extended dispersion zone
Adequately ventilated compressor areas Ventilation prevents accumulation
Ventilated basements below grade Mechanical ventilation removes vapors
Adjacent to Division 1 with vapor barriers Physical separation but proximity risk

Division 2 Extent Guidelines

Configuration Division 2 Extent
From Division 1 boundary Additional 10-20 ft depending on source
Outdoor flanged piping (>2" NPS) 15-25 ft radius from flanges
Pump seals (outdoor) 10 ft radius, 3 ft above grade
Relief valve discharge (beyond Div 1) 15 ft radius from 5 ft boundary

Ventilation Impact

Adequate ventilation can reduce a Division 1 area to Division 2, or reduce Division 2 to non-hazardous. "Adequate ventilation" is typically defined as a minimum of 1 CFM per square foot of floor area, or 4 air changes per hour, with intake at low level and exhaust at high level.

Equipment Requirements for Division 2

Division 2 areas allow more flexibility in equipment selection but still require protection:

  • General-purpose enclosures - Permitted if no arcing components
  • Non-incendive circuits - Normal operation cannot ignite
  • Hermetically sealed devices - Contacts sealed against atmosphere
  • Non-sparking equipment - No arcing during normal operation
  • Restricted breathing enclosures - Limited air exchange with atmosphere

Common Misunderstanding

Division 2 does not mean "safe" or "non-hazardous." It means hazardous conditions are possible but not expected during normal operations. All equipment must still be suitable for the Group D gas classification and rated for Division 2 service.

5. Non-Hazardous (Unclassified) Areas

Non-hazardous or unclassified areas are locations where flammable gas-air mixtures are not expected under normal or abnormal conditions. Standard industrial electrical equipment may be used in these areas.

Typical Non-Hazardous Locations

Location Requirements for Non-Hazardous Classification
Control rooms Vapor-tight barrier, positive pressure from clean air
Motor control centers (separate building) Physical separation, no gas piping inside
Administration buildings Outside classified area boundaries
General yard areas Beyond Division 2 boundaries, outdoor
Buildings with low-pressure fuel gas <100 psig fuel gas, vented to outside

Control Room Requirements

Control rooms in natural gas facilities can be classified as non-hazardous if they meet specific requirements:

Control Room Design Criteria

  • Vapor-tight construction - All penetrations sealed
  • Positive pressurization - Minimum 0.1 inches water gauge
  • Clean air source - Air intake from non-hazardous area
  • Self-closing doors - Maintain pressure when opened
  • Gas detection - Alarm at 20% LEL in HVAC intake
  • Emergency ventilation - Manual or automatic purge capability

Adequately Ventilated Areas

Some areas that would otherwise be classified can be declassified with adequate ventilation:

Ventilation Requirement Result
Continuous ventilation, 1 CFM/ft² May reduce Division 1 to Division 2
4+ air changes/hour with low intake May reduce Division 2 to non-hazardous
Open construction (50%+ wall area open) May reduce extent of classified areas

6. Zone Classification System (IEC)

The Zone system (NEC Article 505, IEC 60079) provides an alternative classification method that is more granular than the Division system. It divides hazardous areas into three zones based on the duration of the hazardous atmosphere.

Zone Duration Approximate Division Equivalent
Zone 0 Continuous or >1000 hours/year Most restrictive Division 1
Zone 1 Likely during normal operation (10-1000 hr/yr) Division 1
Zone 2 Only abnormal conditions (<10 hr/yr) Division 2

Zone vs. Division Comparison

Feature Division System Zone System
Categories 2 (Division 1, 2) 3 (Zone 0, 1, 2)
Origin North American (NEC) International (IEC)
Equipment marking Class/Division/Group Zone/Group/EPL
Typical US use Traditional, widely used Growing adoption, especially multinational

US Practice

Most US natural gas facilities continue to use the Division system due to familiarity and existing equipment inventory. The Zone system is permitted by NEC but is more commonly used by companies with international operations or when using European-manufactured equipment.

7. Equipment Selection

Selecting the correct electrical equipment for hazardous areas requires matching the equipment rating to the area classification. Equipment must be listed and labeled for the specific Class, Division (or Zone), and Group.

Protection Techniques

Technique Division 1 Division 2 Description
Explosion-proof (XP) Yes Yes Contains explosion, prevents propagation
Intrinsically safe (IS) Yes Yes Energy limited below ignition threshold
Purged/Pressurized (Type X, Y, Z) Yes (X, Y) Yes (Z) Positive pressure prevents gas entry
Non-incendive No Yes Normal operation cannot ignite
Hermetically sealed No Yes Fused/welded closure
Oil immersion Yes Yes Contacts immersed in oil

Intrinsically Safe Systems

Intrinsically safe (IS) equipment is designed so that electrical energy is limited to levels that cannot cause ignition of the hazardous atmosphere. This is achieved through energy-limiting barriers and careful circuit design.

IS System Requirements

  • Associated apparatus - Barriers, isolators in safe area
  • Field devices - Simple apparatus (thermocouples, RTDs, switches)
  • Wiring - Dedicated conduit, blue jacket cables
  • Documentation - Entity parameters must be verified
  • Installation - Separation from non-IS circuits

Equipment Marking

Equipment suitable for hazardous locations will be marked with its ratings:

Example Equipment Marking:

Class I, Division 1, Groups C & D, T3

This equipment is suitable for Division 1 areas with Group C or D gases, with a maximum surface temperature of 200°C (T3 rating).

Temperature Class

Equipment must have a maximum surface temperature below the auto-ignition temperature of the gas. Natural gas (methane) has an auto-ignition temperature of approximately 580°C (1076°F).

T-Code Max Surface Temp (°C) Max Surface Temp (°F)
T1 450 842
T2 300 572
T2A 280 536
T2B 260 500
T2C 230 446
T2D 215 419
T3 200 392
T3A 180 356
T3B 165 329
T3C 160 320
T4 135 275
T4A 120 248
T5 100 212
T6 85 185

Natural Gas T-Code

For natural gas (methane) with an AIT of 580°C, equipment rated T1 through T3 is typically acceptable. T1 rated equipment (450°C max) provides adequate margin below the 580°C auto-ignition temperature. However, if heavier hydrocarbons are present, lower T-code ratings may be required.

8. Documentation Requirements

Proper documentation of electrical area classification is essential for initial design, ongoing operations, and regulatory compliance. Documentation should be maintained throughout the facility lifecycle.

Required Documentation

Document Purpose Update Frequency
Area Classification Drawings Show extent of Division 1, 2, and non-hazardous areas With any process change
Classification Basis Document Engineering basis for each classification decision With any process change
Equipment Schedule List all electrical equipment with ratings and locations Annual verification
IS Loop Drawings Entity parameter verification for IS circuits With any circuit change
Inspection Records Document ongoing compliance inspections Per inspection schedule

Area Classification Drawing Content

Area classification drawings should include:

  • Plan views showing horizontal extent of all classified areas
  • Elevation views showing vertical extent
  • Clear identification of Division 1, Division 2, and non-hazardous boundaries
  • Location of all release sources (vents, reliefs, seals, flanges)
  • Building outlines and ventilation openings
  • Reference to applicable codes and standards
  • Revision history and approval signatures

Management of Change

Any modification to process equipment, piping, or ventilation systems requires review of area classification. Even seemingly minor changes (adding a sample point, relocating equipment) can affect classification boundaries. All changes should be documented through the facility's Management of Change (MOC) process.

Inspection and Maintenance

Regular inspection of electrical installations in hazardous areas is required to ensure ongoing compliance:

Inspection Item Frequency Standard Reference
Visual inspection of enclosures Monthly NFPA 70B
Verify equipment ratings match area Annual NEC 500
Check conduit seals Annual NEC 501.15
IS barrier function test Per manufacturer -
Purge system verification Monthly NFPA 496

Related Resources