1. District Regulator Overview
District regulators are the workhorse of gas distribution networks. They reduce pressure from the high-pressure (HP) distribution system (typically 30-100 psig) to the low-pressure (LP) distribution system (typically 0.25-2.0 psig or 7-56 inches water column). A single district regulator station may serve anywhere from 50 to 5,000 residential customers through the LP main network.
Unlike town border stations that operate at high pressures with sophisticated pilot-operated regulators and metering, district regulators are often simple, self-operated (spring-loaded) devices installed in underground vaults or small above-grade enclosures. Their design priority is reliability and stable outlet pressure, because LP distribution systems have very narrow pressure tolerances. Burner appliances require stable supply pressure for safe, efficient operation.
District Regulator vs. Service Regulator
It is important to distinguish between district regulators and service regulators (customer meter-set regulators):
- District regulators: Reduce HP main pressure to LP main pressure. Serve multiple customers through downstream LP mains. Located in vaults at street intersections or distribution node points. Sized for aggregate peak demand of the served district.
- Service regulators: Located at each customer meter set. Reduce service line pressure (HP or LP) to appliance delivery pressure (typically 7 inches WC or 0.25 psig). Sized for individual customer peak demand. Include integral relief or vent provisions.
Installation Types
Underground vault
Most common
Concrete or fiberglass vault below grade. Provides noise reduction and weather protection. Must have ventilation per 49 CFR 192. Requires confined space entry for maintenance.
Above-grade cabinet
Easy maintenance
Metal cabinet on concrete pad. Allows tool-free access for inspection. Higher noise impact on neighbors. Must be fenced or locked per security requirements.
Curb box
Small stations
Small underground box with removable cover. Limited to small regulators (1-inch or less). Used for very small districts or individual large commercial customers.
Building interior
Special applications
Inside a building utility room. Requires gas detection and ventilation. Used when outdoor installation is impractical (dense urban areas).
LP system pressure control: Low-pressure distribution systems operate with very small pressure margins. The minimum delivery pressure at any customer meter must be at least 6 inches WC (0.22 psig), while the maximum must not exceed the LP main MAOP (typically 14 inches WC or 0.50 psig per 49 CFR 192). This narrow band of approximately 8 inches WC total pressure budget must accommodate the district regulator droop, main pressure drop, and service line losses. This is why droop performance is so critical for district regulators.
2. Diversity Factors & Load Estimation
The diversity factor is the ratio of actual peak demand to the total connected appliance load. Not all customers use gas at the same time or at maximum rate, so the actual system peak is significantly less than the sum of all connected loads. Accurate diversity factor selection is essential for proper regulator sizing: too low leads to oversizing (hunting, poor control), too high leads to undersizing (inadequate pressure at peak demand).
Diversity Factor by Customer Count
| Number of Customers | Heating Climate | Moderate Climate | Cooling-Dominated |
| 1-10 | 0.80 | 0.70 | 0.50 |
| 11-25 | 0.70 | 0.60 | 0.45 |
| 26-50 | 0.65 | 0.55 | 0.40 |
| 51-100 | 0.60 | 0.50 | 0.35 |
| 101-250 | 0.55 | 0.45 | 0.30 |
| 251-500 | 0.50 | 0.40 | 0.30 |
| 501+ | 0.45 | 0.35 | 0.25 |
Connected Load Estimation
Residential Load per Customer (typical):
Space heating: 80,000-120,000 BTU/hr (furnace)
Water heating: 30,000-50,000 BTU/hr (tank heater)
Cooking range: 65,000 BTU/hr (all burners + oven)
Clothes dryer: 22,000 BTU/hr
Fireplace: 30,000-60,000 BTU/hr (log set)
Typical total connected load per residence:
Northern climate: 180,000-250,000 BTU/hr
Southern climate: 100,000-150,000 BTU/hr
Peak demand per customer:
Northern: 180,000 × 0.60 = 108,000 BTU/hr ≈ 106 SCFH
Southern: 100,000 × 0.45 = 45,000 BTU/hr ≈ 44 SCFH
For 200 customers (northern):
Connected = 200 × 200,000 = 40,000,000 BTU/hr
Diversity = 0.55
Peak = 40,000,000 × 0.55 = 22,000,000 BTU/hr = 21,569 SCFH
Growth factor: When sizing district regulators, apply a 20-30% growth factor to the calculated peak demand to accommodate future customer additions and load growth within the district. This is particularly important because replacing an undersized regulator in an underground vault is expensive and disruptive. Most utilities design for 10-20 year projected growth.
3. Cv Sizing & Selection
District regulator Cv calculation follows the same ISA 75.01 methodology as other gas regulators, but with particular attention to the large pressure ratio typical of HP-to-LP service. The pressure drop ratio for a 60 psig to 0.25 psig application is approximately 0.98, which is well above the critical pressure ratio and results in choked flow conditions.
Sizing for Choked Flow
District Regulator Cv (HP to LP, choked flow typical):
For x ≥ xT (choked):
Cv = Q / (N8 × P1 × (2/3) × sqrt(xT / (SG × T × Z)))
Example:
Q = 20,000 SCFH, P1 = 60 psig (74.7 psia), P2 = 0.25 psig (14.9 psia)
x = (74.7 - 14.9) / 74.7 = 0.800
xT = 0.70 for self-operated regulator
x > xT → CHOKED
Cv = 20,000 / (1360 × 74.7 × 0.667 × sqrt(0.70/(0.60×519.67×1.0)))
Cv = 20,000 / (1360 × 74.7 × 0.667 × 0.0454)
Cv = 20,000 / 3,077 = 6.5
Select 1-1/4" self-operated (Cv = 20) or 1" pilot-operated (Cv = 18)
Safety factor: 6.5 × 1.3 = 8.5 — 1" regulator at Cv = 12 is borderline
Recommend 1-1/4" self-operated for adequate margin
Regulator Selection Criteria
- Type selection: Self-operated (spring-loaded) regulators are preferred for district service up to about 2-inch size due to lower cost and simpler maintenance. Above 2-inch, pilot-operated regulators provide better lockup and droop performance.
- Oversizing limit: Do not exceed 4:1 ratio of selected Cv to required Cv. Oversized regulators oscillate (hunt) at low flow conditions, which causes premature diaphragm failure and unstable outlet pressure.
- Outlet pressure class: For LP service (under 2 psig), select regulators specifically rated for low-pressure service with spring ranges appropriate for the set point. Standard industrial regulators may not have fine enough adjustment for LP set points.
4. Lockup & Droop Analysis
Lockup and droop are the two most important performance characteristics for district regulators serving LP systems. Together, they determine the operating pressure envelope of the downstream distribution system.
Lockup
Lockup Pressure:
Lockup = outlet pressure at zero flow (all customers off)
P_lockup = P_set × (1 + lockup%)
Typical lockup values:
- Pilot-operated: 1-2% above set point
- Self-operated: 3-5% above set point
- Weight-loaded: 0.5-1% above set point
Example: Set point = 7.0 in WC (0.253 psig)
Self-operated lockup at 5%:
P_lockup = 7.0 × 1.05 = 7.35 in WC (0.266 psig)
LP main MAOP = 14 in WC (0.506 psig)
Lockup margin = 14 - 7.35 = 6.65 in WC (acceptable)
If lockup were 10%: 7.0 × 1.10 = 7.7 in WC
Still acceptable (6.3 in WC margin to MAOP)
Droop
Droop (Proportional Band):
Droop = decrease in outlet pressure from zero flow to maximum flow
P_at_max_flow = P_set × (1 - droop%)
Typical droop values:
- Pilot-operated: 2-5%
- Self-operated: 5-10%
Example: Set point = 7.0 in WC, Self-operated droop = 8%
P_at_max_flow = 7.0 × (1 - 0.08) = 6.44 in WC
Minimum customer delivery pressure = 6.0 in WC
Available main pressure drop budget = 6.44 - 6.0 = 0.44 in WC
This is very tight! Main sizing must be checked carefully.
If droop is too high, consider:
1. Upgrade to pilot-operated regulator (3-5% droop)
2. Increase regulator size (reduces droop by reducing load fraction)
3. Raise set point (if MAOP permits)
Pressure Budget Analysis
| Component | Pressure (in WC) | Cumulative |
| Regulator set point | 7.0 | 7.0 |
| Less: Regulator droop (8%) | -0.56 | 6.44 |
| Less: Main pressure drop | -0.30 | 6.14 |
| Less: Service line drop | -0.10 | 6.04 |
| Customer meter delivery | | 6.04 |
| Minimum required | | 6.00 |
| Margin | | 0.04 in WC |
Low-pressure system design: The pressure budget analysis above illustrates why LP system design is so challenging. With only 0.04 in WC margin, any increase in demand, any degradation in regulator droop performance, or any increase in main friction losses could result in inadequate delivery pressure. This is why modern distribution design increasingly uses medium-pressure (2-60 psig) mains with individual service regulators at each customer, eliminating the LP main and district regulator entirely.
5. Design Examples
Example 1: Residential District
Given:
Inlet: 60 psig HP distribution main
Outlet: 7 in WC (0.253 psig) LP distribution
Customers: 150 residential (northern climate)
Average connected load: 200,000 BTU/hr per customer
Step 1: Total connected load
Total = 150 × 200,000 = 30,000,000 BTU/hr
Step 2: Diversity factor (150 customers, heating climate)
DF = 0.58 (interpolated from table)
Step 3: Peak demand
Peak = 30,000,000 × 0.58 = 17,400,000 BTU/hr
Q = 17,400,000 / 1020 = 17,059 SCFH
Step 4: Apply 25% growth factor
Q_design = 17,059 × 1.25 = 21,324 SCFH
Step 5: Cv calculation (choked flow, x = 0.98)
P1 = 74.7 psia, Y = 2/3, xT = 0.70
Cv = 21,324 / (1360 × 74.7 × 0.667 × 0.0454)
Cv = 21,324 / 3,077 = 6.93
Step 6: Select regulator
Required Cv × 1.3 = 9.0
Select 1-1/4" self-operated (Cv = 20)
Load fraction = 6.93 / 20 = 35% (good operating point)
Step 7: Droop check
Droop = 8% × 0.35 = 2.8%
Outlet at peak = 7.0 × (1 - 0.028) = 6.80 in WC (acceptable)
Example 2: Commercial District
Given:
Inlet: 60 psig HP distribution
Outlet: 2 psig (medium-pressure LP)
Loads: Shopping center + 50 small commercial
Total connected: 15,000,000 BTU/hr
Diversity factor: 0.75 (commercial loads are more coincident)
Step 1: Peak demand
Peak = 15,000,000 × 0.75 = 11,250,000 BTU/hr
Q = 11,250,000 / 1020 = 11,029 SCFH
Step 2: With 20% growth
Q_design = 11,029 × 1.20 = 13,235 SCFH
Step 3: Cv calculation
P1 = 74.7 psia, P2 = 16.7 psia
x = (74.7 - 16.7) / 74.7 = 0.776
xT = 0.70, choked
Cv = 13,235 / (1360 × 74.7 × 0.667 × 0.0454)
Cv = 13,235 / 3,077 = 4.30
Step 4: Select regulator
Required Cv × 1.3 = 5.6
Select 1" self-operated (Cv = 12)
Or 1" pilot-operated (Cv = 18) for better droop control
With pilot-operated:
Load fraction = 4.30 / 18 = 24%
Droop = 3% × 0.24 = 0.7% (excellent)
Maintenance schedule: District regulators should be inspected annually per utility maintenance procedures and 49 CFR 192 Subpart M requirements. Inspection includes checking set pressure, lockup, vent operation, and physical condition of diaphragm and seat. In corrosive soil conditions, underground vaults should be inspected for water accumulation, structural integrity, and cathodic protection continuity. Many utilities are transitioning to smart monitoring with pressure transducers and cellular telemetry to detect regulator degradation between scheduled inspections.